Extended Parameters
Setting FTP Parameters
- FTP is a universal standard protocol without any security authentication mechanism. Data transmitted by FTP is not encrypted. To reduce network security risks, the IP address of the connected third-party FTP server is left blank by default. This protocol can transmit the running data of PV plants, which may cause user data breach. Therefore, exercise caution when using this protocol. Users are liable for any loss caused by the enabling of the FTP protocol (non-secure protocol). Users are advised to take measures at the PV plant level to reduce security risks, or use Huawei management system to mitigate the risks.
- The FTP function is used to access a third-party NMS. The SmartLogger can report the configuration information and running data of the managed plant system through the FTP. A third-party NMS can access Huawei devices with proper configurations.
Because of permission restriction, log in as Advanced User. Choose to access the target page.
- FTP server can be set to the domain name or IP address of the FTP server. If FTP server is set to the domain name of the FTP server, ensure that the address of the DNS server on the Ethernet page is set correctly.
- User name and Password indicate the user name and password that need to be entered when you log in to the FTP server.
- After setting Remote directory, you can create a subdirectory in the default data upload directory (specified by the FTP server).
- If Data export is set to Enable, you can set the SmartLogger to report data regularly or at a specified time. If you set the SmartLogger to report data regularly, you can choose whether to report all data or only the incremental data of a day each time.
- In FTP file format, Format 2 has two more information points than Format 1: E-Day (current-day energy yield) and E-Total (total energy yield). Format 3 has more information points than the other two format files: multimeter, PID module, user-defined device, and SmartLogger data.
- The displayed formats of the file name and time can be set in File Name and Time format. Y, M, D, H, and m represent the year, month, day, hour (24-hour system), and minute respectively.
Error Code |
Troubleshooting Suggestion |
Error Code |
Troubleshooting Suggestion |
---|---|---|---|
0x1002 |
No FTP server address is configured. Configure the address correctly. |
0x1003 |
|
0x1004 |
No FTP user name is configured. Configure the user name correctly. |
0x1005 |
No FTP user password. Configure the user password correctly. |
0x3001 |
|
0x3002 |
|
0x3007 |
Check whether data is allowed to be uploaded through a client to the third-party FTP server. |
0x3008 |
Check whether there is a SmartLogger data upload directory on the third-party FTP server. |
If the error code is not listed in this table, provide SmartLogger run logs and contact Huawei technical support.
Setting Email Parameters
The SmartLogger can send emails to inform users of the energy yield, alarm, and equipment status information of the PV plant system, helping users to know the running conditions of the PV plant system in time.
When using this function, ensure that the SmartLogger can be connected to the configured email server and that the Ethernet parameters and email parameters for the SmartLogger are correctly set. Ensure that no password is set between the SmartLogger and the email server.
Because of permission restriction, log in as Advanced User. Choose to access the target page.
- SMTP Server can be set to the domain name or IP address of the SMTP server.
If it is set to the domain name of the SMTP server, ensure that the address of the DNS server is set correctly.
- Encryption mode: Set the encryption mode supported by mailboxes. Encryption is supported by most of the mainstream mailboxes such as Outlook, @qq.com, @126.com, @163.com, and @sina.com.
- SMTP Port specifies the port used for sending emails.
- User name and Password specify the user name and password used for logging in to the SMTP server.
- Send address specifies the sender's email address. Ensure that the sender's email server is the same as the server specified by SMTP server.
- You can click Send test mail to check whether the SmartLogger can successfully send emails to users.
Error Code |
Troubleshooting Suggestion |
Error Code |
Troubleshooting Suggestion |
---|---|---|---|
0x2002 |
|
0x2003 |
|
0x200b |
|
0x4016 |
|
0x406e |
Confirm the encryption mode and port supported by the mailbox, and check whether they are correctly configured. |
0x8217 |
|
0xa003 |
Check whether the domain name or IP address of the SMTP server are correct. |
0xa005 |
Check whether the user name is correct. |
0xa006 |
Check whether the user password is correct. |
0xe002 |
No domain name or IP address is configured for the SMTP server. Configure the domain name and IP correctly. |
0xe003 |
Configure the addresses for sending and receiving emails correctly. |
Other error codes |
Provide SmartLogger run logs and contact Huawei technical support. |
If the error code is not listed in this table, provide SmartLogger run logs and contact Huawei technical support.