Connecting to a PID
This section describes how to connect the SmartLogger to a PID.
Context
There are three RS485 ports in the SmartLogger. For the port descriptions, see Context in Connecting the SmartLogger to the SUN2000.
Procedure
- Connect one end of the cable delivered with the PID to the RS485 port of the PID.
- Connect the other end of the cable to a Surge port of the
RS485 signal SPD. For details, see 2–4 in Procedure in Connecting the SmartLogger to the SUN2000.
Verify that the brown cable (RS485A) of the PID module is connected to Surge port 1 or 7 on the RS485 signal SPD, and that the black cable (RS485B) is connected to Surge port 5 or 11 on the RS485 signal SPD.