No relevant resource is found in the selected language.
Your browser version is too early. Some functions of the website may be unavailable. To obtain better user experience, upgrade the browser to the latest version.
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document.
Note: Even the most advanced machine translation cannot match the quality of professional translators.
Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Dry Contact Remote Control
Dry Contact Remote Control
If ports of DI1–DI4 have been configured in Dry contact remote shutdown, Dry contact remote control is unavailable.
Set Reactive power control mode to Dry contact remote control.
Figure 8-8 Dry contact remote control
A maximum of 16 levels are supported for power factors.
"√" indicates low level. When connecting to GND2, the four DI
ports of the SmartLogger are low-level ports. If not connected, the
ports are high-level ports.
The status combination of DI1(GND2)–DI4(GND2) should differ from
each other. Otherwise, abnormal command parsing will occur.
If the actual input DI signal is inconsistent with that configured
on the WebUI, the SmartLogger does not allow the SUN2000 to generate
reactive power and the Abnormal Reactive Schedule alarm is generated.
If Active Power Control is set to AI remote control, Dry contact remote control is unavailable for Reactive Power Control.