Dry contact remote shutdown
You can remotely shut down dry contacts on the WebUI.
- The OVGR sends dry contact signals and can be connected to any DI port of the SmartLogger. Set related parameters based on the actual connection between the OVGR and the SmartLogger. Otherwise, the dry contact remote shutdown function cannot be implemented.
- Set Connection port based on the actual connection between the OVGR and the SmartLogger.
- Effective dry contact status can be set to Close or Open. If OVGR Shutdown Setting is set to Enable and Effective dry contact status is set to Close, the SmartLogger sends the inverter remote shutdown command only when the DI port specified by connection port is closed.
- OVGR Shutdown Setting can be set to Enable or Disable. Set OVGR Shutdown Setting as required.
- Cubicle alarm enabling can be set to Enable or Disable. If Cubicle alarm enabling is set to Enable, if the dry contact signal is effective and the Cubicle is abnormal, an alarm indicating abnormal Cubicle is generated.