Percentage Fixed-value Limitation (Open Loop)
The SmartLogger provides simplified active power percentage configuration as well as power control automation, that is, to automatically adjust the active power derating percentage in different periods of the day.
Parameter |
Description |
---|---|
Set this parameter to Percentage fixed-value limitation (open loop) to control the maximum output power of the inverter by time segment. |
|
If the inverters are required to run with specified maximum power in certain periods of a day, add setting records based on site requirements. When multiple time points are set, the inverters will run with the maximum power specified for the time point that is earlier than and the closest to the system current time point. For example, if you add 00:00:00 and 12:00:00 on the WebUI and the system current time point is 14:30:00, the inverters will run with the maximum power specified for 12:00:00. |
|