Remote Output Control
Before setting the parameters for remote output control, synchronize the clock source of the server. For details, see Setting the Date and Time.
- Clock source: Set NTP.
- Server: Set the server IP address or domain name.
- NTP synchronization test: Check the time synchronization status.
Set Active power control mode to Remote output control.
- Control area: Set the areas for remote output control. To enable the function in some areas, the license needs to be imported and enabled.
- Output control duration: Set the time required for the inverter to change its output power from 0% to 100% or from 100% to 0%.
- PV plant ID: Set the ID assigned by the power company to the SmartLogger.
- Remote output control server: Set the server IP address or domain name.
- If the connection between the SmartLogger and the server is abnormal, obtain the output control file in .data format from the website of the power company and import the file.
- After the SmartLogger connects to the server, you can export the relevant file.