Alarms
This topic describes the common faults in the SmartLogger and the troubleshooting measures.
Table 9-2 describes the common faults and the troubleshooting measures.
Alarm ID |
Alarm |
Alarm Severity |
Alarm Sub-ID |
Causes |
Measure |
---|---|---|---|---|---|
1100 |
Abnormal P-Control |
Major |
1 |
Under the active power AI remote control mode, the feedback command data of the AO port cannot be read due to the ADAM fault, power disconnection, or abnormal link. |
|
1101 |
Abnormal Q-Control |
Major |
1 |
Under the reactive power Dry contact remote control mode, the four DI ports read commands beyond the configuration. |
|
1102 |
Abnormal Meter Data |
Major |
1 |
The power meter cannot properly send feedback signals to a third-party scheduling device due to the ADAM fault, power disconnection, or abnormal link. |
|
1103 |
Breaker Disconnect |
Major |
1 |
The general AC circuit breaker at the grid-tied point is OFF. |
Check whether the disconnection of the circuit breaker is a normal operation. Otherwise, contact the service engineer to restore the connection. |