Dry Contact Remote Control
Dry Contact Remote Control
If ports of DI1–DI4 have been configured in Dry contact remote shutdown, Dry contact remote control is unavailable.
Set Active power control mode to Dry contact remote control.
Figure 8-4 Dry contact remote control
A maximum of 16 levels are supported for the percentages.
"√" indicates a low level. When connecting to GND1, the four DI
ports of the SmartLogger are low-level ports. If not connected, the
ports are high-level ports.
The status combination of DI1(GND1)–DI4(GND1) should differ from
each other. Otherwise, abnormal command parsing will occur.
If the actual input DI signal is inconsistent with that configured
on the WebUI, the SmartLogger controls the SUN2000 to work at full
power and the Abnormal Active Schedule alarm
is generated.