Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Powering On a Server

Powering On a Server

This topic describes how to power on a server.

Procedure

  1. Ensure that the power cables and ground cables are securely connected with correct polarity and good contact.
  2. Ensure that the input power supply for the AC PDB is off. Use a multimeter to test the resistance between the power outputs of the AC PDB and between the BGND and PGND. It is required that short circuit not occur between power outputs or between the BGND and PGND.
  3. Switch on the power of a rack.
  4. Switch on the circuit breakers of PDBs for the rack. The power supply for equipment in the rack is available.
  5. Press the power button on the chassis of the server to power on the server.

    Figure 5-2 shows the power button of the 2288H V5 server.

    Figure 5-2 2288H V5 power button

    Figure 5-3 shows the power button of the RH5885H V3 server.

    Figure 5-3 RH5885H V3 power button