SUN2000-(50KTL, 60KTL, 65KTL)-M0 User Manual

This document describes the SUN2000-50KTL-M0, SUN2000-60KTL-M0 and SUN2000-65KTL-M0 in terms of its installation, electrical connections, commissioning, maintenance, and troubleshooting.
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Technical Specifications

Technical Specifications

Efficiency

Item

SUN2000-50KTL-M0

SUN2000-60KTL-M0

SUN2000-65KTL-M0

Maximum efficiency

98.70%

98.70% (380 V/400 V)

98.90% (480 V)

98.90%

European efficiency

98.50%

98.50% (380 V/400 V)

98.70% (480 V)

98.70%

Input

Item

SUN2000-50KTL-M0

SUN2000-60KTL-M0

SUN2000-65KTL-M0

Maximum input power

56,200 W

67,400 W

73,500 W

Maximum input voltagea

1100 V

Operating voltage rangeb

200–1000 V

Maximum input current (per MPPT)

22 A

Maximum short-circuit current (per MPPT)

30 A

Maximum SUN2000 backfeed current to the PV array

0 A

Minimum startup voltage

200 V

Full power MPPT voltage range

520–800 V

520–800 V (380 V/400 V), 600–850 V (480 V)

600–850 V

Rated input voltage

600 V (380 V/400 V), 620 V (415 V)

600 V (380 V/400 V), 720 V (480 V)

720 V

Number of inputs

12

Number of MPP trackers

6

Note a: The maximum input voltage is the upper threshold of the DC voltage. If the input voltage exceeds the threshold, the solar inverter may be damaged.

Note b: If the input voltage is beyond the operating voltage range, the solar inverter cannot work properly.

Output

Item

SUN2000-50KTL-M0

SUN2000-60KTL-M0

SUN2000-65KTL-M0

Rated active power

50 kW

60 kW

65 kW

Maximum apparent power

55 kVA

66 kVA

72 kVA

Maximum active power (cosφ = 1)

55 kW (Can be set to 50 kW)

66 kW (Can be set to 60 kW)

72 kW

Rated output voltagea

220V/380V, 230V/400V, 240V/415V, 3W+(N)b+PE

220V/380V, 230V/400V, 277V/480V, 3W+(N)b+PE

277 V/480 V, 3W+PE

Rated output current

76 A (380 V), 72.2 A (400 V), 69.6 A (415 V)

91.2 A (380 V) 86.7 A (400 V), 72.2 A (480 V)

78.2 A

Adapted grid frequency

50 Hz/60 Hz

Maximum output current

83.6 A (380 V), 79.4 A (400 V), 76.6 A (415 V)

100 A (380 V), 95.3 A (400 V), 79.4 A (480 V)

86.7 A

Power factor

0.8 leading ... 0.8 lagging

Maximum total harmonic distortion (rated power)

< 3%

Note a: The rated output voltage is determined by Grid code, which can be set on the SUN2000 app, SmartLogger, or NetEco.

Note b: Choose whether to connect the neutral wire to the SUN2000-50KTL-M0 and SUN2000-60KTL-M0 based on the application scenario. When it is used in the scenarios without neutral wires, set Output mode to Three-phase, three-wire. When it is used in the scenarios with neutral wires, set Output mode to Three-phase, four-wire.

Protection

Item

SUN2000-50KTL-M0

SUN2000-60KTL-M0

SUN2000-65KTL-M0

Input DC switch

Supported

Anti-islanding protection

Supported

Output overcurrent protection

Supported

Input reverse polarity protection

Supported

PV string fault detection

Supported

DC surge protection

Type II

AC surge protection

Type II

Insulation resistance detection

Supported

Residual current monitoring unit (RCMU)

Supported

Overvoltage category

PV II/AC III

Built-in PID repairc

Optional

Optional

Not supported

Note c: When the SUN2000 is disconnected from the grid and stops working, the built-in PID can achieve the PV– positive offset of the PV module. (PV– positive offset refers to raising the voltage between PV– and the ground to above 0 V through voltage compensation.) When designing a power plant, confirm with the PV module manufacturer that the anti-PID voltage compensation direction of the PV module is the same as the direction of the PV– positive offset. Otherwise, PV modules may be damaged.

For the SUN2000 that supports built-in PID repair, when Built-in PID running mode is set to Repair, there is repair voltage between PV modules and the ground at night. If you need to maintain PV modules at night, power off the SUN2000 to avoid electric shocks.

Display and Communication

Item

SUN2000-50KTL-M0

SUN2000-60KTL-M0

SUN2000-65KTL-M0

Display

LED, Bluetooth module+app, USB data cable+app, WLAN module+app

Communication networking mode

MBUS/RS485

Common Parameters

Item

SUN2000-50KTL-M0

SUN2000-60KTL-M0

SUN2000-65KTL-M0

Dimensions (W x H x D)

1075 mm x 555 mm x 300 mm

Net weight

74 kg±1 kg

72 kg±1 kg

Operating temperature

–25°C to +60°C

Cooling mode

Natural convection

Highest operating altitude

4000 m

Humidity

0%–100% RH

Input terminal

Amphenol Helios H4

Output terminal

Cable gland+OT terminal

Ingress Protection Rating

IP65

Topology

Transformerless