Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ODC_DOOR_OPEN

ODC_DOOR_OPEN

Description

The ODC_DOOR_OPEN alarm indicates that the door of an outdoor cabinet is open.

Attribute

Alarm Severity Alarm Type
Critical Equipment alarm

Parameters

None.

Impact on the System

The temperature, ambient humidity, and dust-proof capability of the equipment are affected by the external environment. In addition, the equipment may be damaged or stolen.

Possible Causes

Possible causes of this alarm are as follows:

  • The door access alarm configuration is incorrect.
  • The cabinet door is opened by someone.
  • The cable between the sensor and the monitoring equipment is incorrectly connected.
  • The sensor is faulty.
  • The monitoring equipment is faulty.
  • No door status sensor is installed.

Procedure

  1. Check whether the door access alarm configuration is consistent with the configuration plan.
    If... Then...

    The door access alarm configuration is consistent with the configuration plan

    Go to the next step.

    The door access alarm configuration is inconsistent with the configuration plan

    Configure the door access alarm enabling status correctly.
  2. Close the cabinet door.
  3. Check whether the cable between the sensor and the monitoring equipment is correctly connected.
    If... Then...

    The cable is connected incorrectly or loosely

    Connect the cable correctly and securely.

    The cable is deteriorating or damaged

    Replace the cable.

    The cable is connected correctly

    Go to 4.
  4. Rectify the fault on the sensor. Then, check whether the alarm is cleared.
    If... Then...

    The alarm is cleared

    No further action is required.

    The alarm persists

    Go to 5.
  5. Rectify the fault on the monitoring equipment.
    If... Then...

    The alarm is cleared

    No further action is required.

    The alarm persists

    Go to 6.
  6. Install a door status sensor and enable the door access alarm.