Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ENVTEMP1_SENSOR_FAIL

ENVTEMP1_SENSOR_FAIL

Description

The ENVTEMP1_SENSOR_FAIL alarm indicates that ambient temperature sensor 1 fails.

Attribute

Alarm Severity Alarm Type

Major

Environment alarm

Parameters

None.

Impact on the System

The equipment cannot collect the data of ambient temperature sensor 1 on the PMU.

Possible Causes

Possible causes of this alarm are as follows:

  • Ambient temperature sensor 1 is not installed.
  • Ambient temperature sensor 1 is incorrectly connected.
  • Ambient temperature sensor 1 is faulty.
  • The control board of the cabinet is faulty.

Procedure

  1. Check whether ambient temperature sensor 1 is installed.

    If...

    Then...

    Ambient temperature sensor 1 is not installed

    Install ambient temperature sensor 1 correctly.

    Ambient temperature sensor 1 is installed

    Go to the next step.

  2. On the U2000, check whether the ENVTEMP1_SENSOR_FAIL alarm is cleared. If the ENVTEMP1_SENSOR_FAIL alarm persists, check whether ambient temperature sensor 1 is correctly connected or the cable is intact.

    If...

    Then...

    Ambient temperature sensor 1 is incorrectly connected

    Connect ambient temperature sensor 1 correctly.

    The cable is damaged

    Replace the cable.

    Ambient temperature sensor 1 is correctly connected and the cable is intact

    Go to the next step.

  3. On the U2000, check whether the ENVTEMP1_SENSOR_FAIL alarm is cleared. If the ENVTEMP1_SENSOR_FAIL alarm persists, replace ambient temperature sensor 1.
  4. If the ENVTEMP1_SENSOR_FAIL alarm persists after ambient temperature sensor is replaced, replace the cabinet. Then, the ENVTEMP1_SENSOR_FAIL alarm is automatically cleared.

Related Information

None.