Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ENVHUM_SENSOR_FAIL

ENVHUM_SENSOR_FAIL

Description

The ENVHUM_SENSOR_FAIL alarm indicates that the ambient humidity sensor fails.

Attribute

Alarm Severity Alarm Type

Major

Environment alarm

Parameters

None.

Impact on the System

The equipment cannot collect ambient humidity data of the PMU.

Possible Causes

Possible causes of this alarm are as follows:

  • No ambient humidity sensor is installed.
  • The ambient humidity sensor is incorrectly connected.
  • The ambient humidity sensor is faulty.
  • The control board of the cabinet is faulty.

Procedure

  1. Check whether an ambient humidity sensor is installed.
    If... Then...

    No ambient humidity sensor is installed

    Install an ambient humidity sensor correctly.

    An ambient humidity sensor is installed

    Go to the next step.

  2. On the U2000, check whether the ENVHUM_SENSOR_FAIL alarm is cleared. If the ENVHUM_SENSOR_FAIL alarm persists, check whether the ambient humidity sensor is correctly connected or the cable is intact.
    If... Then...

    The ambient humidity sensor is incorrectly connected

    Connect the ambient humidity sensor correctly.

    The cable is damaged

    Replace the cable.

    The ambient humidity sensor is correctly connected and the cable is intact

    Go to the next step.

  3. On the U2000, check whether the ENVHUM_SENSOR_FAIL alarm is cleared. If the ENVHUM_SENSOR_FAIL alarm persists, replace the ambient humidity sensor.
  4. If the ENVHUM_SENSOR_FAIL alarm persists after the ambient humidity sensor is replaced, replace the cabinet. Then, the ENVHUM_SENSOR_FAIL alarm is automatically cleared.

Related Information

None.