OSN 500 550 580 V100R008C50 Commissioning and Configuration Guide 02

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Configuring Sub-Rate Transparent Transmission Services

Configuring Sub-Rate Transparent Transmission Services

Some remote terminal units (RTUs) in the electric power industry can be controlled and managed at remote sites but cannot be remotely managed in the control center in a centralized manner. To resolve this issue, deploy the supervisory control and data acquisition (SCADA) system in the control center and configure point-to-point RS232 serial port services on the transmission devices between the control center and sites.

Networking Diagram

This section describes the networking of NEs.

Figure 2-27 shows the networking diagram for sub-rate transparent transmission services. This solution can transmit sub-rate services at a rate of 0 kbit/s to 19.2 kbit/s. In this example, the V.24 protocol is used as the interface protocol.

Figure 2-27  Networking diagram for sub-rate transparent transmission services
NOTE:

This topic considers the OptiX OSN 580 as an example to describe the board layout. In the case of other products, the configuration method is the same, except for the slots. For the slot information, see the Hardware Description of the relevant product.

Service Planning

This section describes the parameters required for configuring sub-rate transparent transmission services.

Each of NE 1 and NE 2 requires a 64 kbit/s service channel. Table 2-24 provides the timeslot allocation of a 64 kbit/s service channel.

Table 2-24  Timeslot allocation of a 64 kbit/s service channel
NE Board Source E1 Source Timeslot Range Sink E1 Sink Timeslot Range
NE1 7-DXM DDN-19 1 2M-1(SDH_TU-65) 1
NE2 7-DXM DDN-19 1 2M-1(SDH_TU-65) 1
  • The sub-rate services occupy the SDH_TU-65 channel during the transmission at the PCM port side.
  • The sub-rate services occupy the first VC-12 timeslot in the first VC-4 (VC4-1:VC12-1) on the SDH link between NE 1 and NE 2 during the transmission at the SDH network side.
Table 2-25  Parameters for serial port management
Parameter NE1 NE2
Board 7-DXM 7-DXM
Port 7-DXM-19(DDN-19) 7-DXM-19(DDN-19)
Serial Port Rate N*64K N*64K
N Value 1 1
Protocol Mode V.24 Mode V.24 Mode
Working Mode DCE DCE
Phase Mode Normal phase Normal phase
Synchronous Yes Yes
Other parameters Default values Default values
Table 2-26  64 kbit/s service parameters
Parameter NE1 NE2
Board 7-DXM 7-DXM
Direction Bidirectional Bidirectional
Source E1 DDN-19 DDN-19
Source Timeslot Range (e.g. 1, 3-6) 1 1
Sink E1 2M-1(SDH_TU-65) 2M-1(SDH_TU-65)
Sink Timeslot Range (e.g. 1, 3-6) 1 1
Bandwidth 1 1
Table 2-27  SDH service parameters
Parameter NE1 NE2
Level VC12 VC12
Direction Bidirectional Bidirectional
Source Slot 7-DXM 7-DXM
Source VC4 - -
Source Timeslot Range (e.g. 1, 3-6) 65 65
Sink Slot 4-SL41O-1(SDH-1) 4-SL41O-1(SDH-1)
Sink VC4 VC4-1 VC4-1
Sink Timeslot Range (e.g. 1, 3-6) 1 1

Configuration Procedure

This section describes the procedure for configuring sub-rate transparent transmission services.

Prerequisites

Procedure

  1. Configure a pulse code modulation (PCM) service on NE 1.
    1. Configure the port for receiving and transmitting a PCM service.



      Click Apply.

      NOTE:

      In this example, retain the default values for the other parameters on the Serial Port Management page. Plan the parameters according to the actual networking. For details about the parameters, see Parameters for Serial Port Management.

    2. Configure a 64 kbit/s service.

    3. Configure the cross-connection between the PCM service and an SDH link.

  2. Configure a PCM service on NE 2.

    Follow instructions in 1 to configure a PCM service on NE 2.

  3. Check whether the service is correctly configured by following instructions in Testing Sub-Rate Services.
  4. Enable the performance monitoring function for the NEs by following instructions in Enabling NE Performance Monitoring.
  5. Back up the configuration data of the NEs by following instructions in Backing Up the NE Configuration Data to the SCC Board.

Follow-up Procedure

Because no RTS or DTR cable is used, RTS and DTR alarms are reported to the NMS, which does not affect services. To mask RTS and DTR alarms for a DXM board, perform the following operations:

  1. In the NE Explorer, select the desired DXM board and choose Alarm > Alarm Suppression.
  2. On the Alarm Suppression page, set Status to Suppressed for DTR and RTS alarms.