Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ALM-0x03000011 PSU Overtemperature (PSU, Major Alarm)

ALM-0x03000011 PSU Overtemperature (PSU, Major Alarm)

Description

Alarm message:

PSU arg1 is overtemperature. 

This alarm is generated when the temperature of a power supply unit (PSU) exceeds the overtemperature major threshold. This alarm is cleared when the temperature is within the normal range.

Alarm object: PSU

Attribute

Alarm ID

Alarm Severity

Auto Clear

0x03000011

Major

Yes

Parameters

Name

Meaning

arg1

Serial number of the PSU.

Impact on the System

Overheating affects the PSU service time and power supply to the system, which causes power-off of the server and interrupts services running on the server.

Possible Causes

  • A fan module is faulty.
  • The equipment room temperature exceeds the normal range.
  • The air inlet is blocked.
  • The air outlet is blocked.
  • The PSU is faulty.

Procedure

  1. Check whether there are fan module alarms.

  2. Replace the faulty fan or fan module. After 5 minutes, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 3.

  3. Check whether the equipment room temperature exceeds the normal range.

  4. Reduce the equipment room temperature to the normal range. After 5 minutes, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 5.

  5. Check whether the air inlet or outlet of the server is blocked.

  6. Clear the blockage. After 5 minutes, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 7.

  7. Replace the PSU. Then, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 8.

  8. Getting Help.