No relevant resource is found in the selected language.

This site uses cookies. By continuing to browse the site you are agreeing to our use of cookies. Read our privacy policy>Search

Reminder

To have a better experience, please upgrade your IE browser.

upgrade

KunLun 9008 V5 Alarm Handling 05

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ALM-0x27000001 PCH Overtemperature (PCH, Minor Alarm)

ALM-0x27000001 PCH Overtemperature (PCH, Minor Alarm)

Description

Alarm message:

PCH temperature (arg1 degreess C) exceeds the overtemperature threshold (arg2 degreess C). 

This alarm is generated when the platform controller hub (PCH) temperature exceeds the overtemperature major threshold. This alarm is cleared when the temperature is within the normal range.

Alarm object: PCH

Attribute

Alarm ID

Alarm Severity

Auto Clear

0x27000001

Minor

Yes

Parameters

Name

Meaning

arg1

Current reading of the sensor.

arg2

Alarm threshold.

Impact on the System

Overheating affects PCH performance. If the alarm persists, the server may power off or restart, which interrupts services and causes data loss.

Possible Causes

  • The equipment room temperature exceeds the normal range.
  • The fan speed is too low.
  • The air inlet or outlet is blocked.
  • The mainboard is faulty.

Procedure

  1. Check whether there are fan module alarms.

  2. Replace the faulty fan or fan module. After 5 minutes, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 3.

  3. Check whether the equipment room temperature exceeds the normal range.

  4. Reduce the equipment room temperature to the normal range. After 5 minutes, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 5.

  5. Check whether the air inlet or outlet of the server is blocked.

  6. Clear the blockage. After 5 minutes, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 5.

  7. Replace the mainboard. After the server is powered on, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 8.

  8. Getting Help.
Translation
Download
Updated: 2019-05-25

Document ID: EDOC1100023838

Views: 101974

Downloads: 16

Average rating:
This Document Applies to these Products
Related Documents
Related Version
Share
Previous Next