No relevant resource is found in the selected language.

This site uses cookies. By continuing to browse the site you are agreeing to our use of cookies. Read our privacy policy>Search

Reminder

To have a better experience, please upgrade your IE browser.

upgrade

KunLun 9008 V5 Alarm Handling 05

Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ALM-0x02000015 Hard Disk Overtemperature (Hard Disk, Minor Alarm)

ALM-0x02000015 Hard Disk Overtemperature (Hard Disk, Minor Alarm)

Description

Alarm message:

The [arg1] disk arg2 temperature (arg3 degrees C) exceeds the threshold (arg4 degrees C). 

This alarm is generated when the hard disk temperature exceeds the overtemperature minor threshold.

Alarm object: hard disk

Attribute

Alarm ID

Alarm Severity

Auto Clear

0x02000015

Minor

Yes

Parameters

Name

Meaning

arg1

Location of the hard disk. For example, front or rear.

arg2

Slot number of the hard disk.

arg3

Current reading of the sensor.

arg4

Alarm threshold.

Impact on the System

Overheating affects hard disk performance and data processing services.

Possible Causes

  • A fan module is faulty.
  • The equipment room temperature exceeds the normal range.
  • The air inlet or outlet is blocked.
  • The hard disk is faulty.

Procedure

  1. Check whether there are fan module alarms.

  2. Replace the faulty fan or fan module. After 5 minutes, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 3.

  3. Check whether the equipment room temperature exceeds the normal range.

  4. Reduce the equipment room temperature to the normal range. After 5 minutes, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 5.

  5. Check whether the air inlet or outlet of the server is blocked.

  6. Clear the blockage. After 5 minutes, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 7.

  7. Replace the faulty hard disk. Then, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 8.

  8. Getting Help.
Translation
Download
Updated: 2019-05-25

Document ID: EDOC1100023838

Views: 87368

Downloads: 16

Average rating:
This Document Applies to these Products
Related Documents
Related Version
Share
Previous Next