Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ALM-0x12000001 Air Inlet Overtemperature (Chassis, Minor Alarm)

ALM-0x12000001 Air Inlet Overtemperature (Chassis, Minor Alarm)

Description

Alarm message:

The air inlet temperature (arg1 degrees C) exceeds the overtemperature threshold (arg2 degrees C).

This alarm is generated when the air inlet temperature exceeds the overtemperature minor threshold.

This alarm is cleared when the temperature is within the normal range.

Alarm object: chassis

Attribute

Alarm ID

Alarm Severity

Auto Clear

0x12000001

Minor

Yes

Parameters

Name

Meaning

arg1

Current reading of the sensor.

arg2

Alarm threshold.

Impact on the System

Overheating affects component performance and server operations.

Possible Causes

  • The ambient temperature exceeds the normal range.
  • The air inlet is blocked.
  • Idle slots or spaces are not installed with filler panels.
  • The component hosting the air inlet temperature sensor is faulty.

Procedure

  1. Check whether the equipment room temperature exceeds the normal range.

  2. Reduce the equipment room temperature to the normal range. After 5 minutes, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 3.

  3. Check whether the server air inlet is blocked.

  4. Clear the blockage. After 5 minutes, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 5.

  5. Check whether there are empty slots in the server.

  6. Install filler panels in empty slots. Then, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 7.

  7. Replace the component where the air inlet temperature sensor is located. Then, check whether the alarm is cleared.

    The location of the air inlet temperature sensor is on the indicator plate in the left mounting ear. Replace the left mounting ear. For details, see "Replacing Parts" in the user guide. Then, check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 8.

  8. Getting Help.