Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ALM-1700001F The Voltage at the +3.3VDD Detection Point Exceeding the Overvoltage Alarm Threshold

ALM-1700001F The Voltage at the +3.3VDD Detection Point Exceeding the Overvoltage Alarm Threshold

Description

Alarm message:

The voltage (xx V) at the +3.3VDD detection point on the CMC mainboard exceeds the overvoltage alarm threshold (xx V).

Attribute

Alarm ID

Alarm Severity

Auto Clear

1700001F

Major

Yes

Parameters

Name

Meaning

Alarm Severity

Indicates the alarm severity.

Alarm Source

Indicates the alarm source.

Subject

Indicates the event body for which an alarm is generated.

Time

Indicates the time when an alarm is generated.

Description

Provides an alarm description.

Event Code

Indicates the event code of an alarm.

Impact on the System

The power supply units (PSUs) may power off, which will affect services.

System Actions

None

Possible Causes

  • The power supply to the CMC is unstable.
  • The upper threshold for major alarms is not properly set for the sensor.
  • Some components on the CMC board are faulty.

Procedure

  1. Check whether the value of Alarm Source in alarm locating parameters is CMC1 or CMC2.

  2. Run the smmget -t sensor -d thresholdall command on the CMC CLI, and check whether the upper threshold for major alarms is set properly.

    The proper threshold for the sensor is as follows:

    +3.3VDD: 3.64 V

  3. Run the smmset -t sensor -d uppercritical -v value command (value indicates the upper threshold for major alarms) on the CMC CLI to change the threshold. Then check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 4.

  4. Run the reboot command on the CMC CLI to restart the CMC. Then check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 5.

  5. Replace the CMC. Then check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 6.

  6. Restart the CMC. Then check whether the alarm is cleared.

    • If yes, no further action is required.
    • If no, go to Step 7.

  7. Contact Huawei technical support.

Clearing

This alarm is cleared when the sensor detects that the voltage is lower than the upper threshold for major alarms.

After the fault is rectified, the system automatically clears the alarm.