Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Environmental Specifications

Environmental Specifications

Table 12-1 describes the environmental specifications of the G560 V5, GP608, and GS608.

Table 12-1 Environmental specifications

Item

Specifications

Temperature

  • Operating temperature: 5°C to 35°C (41°F to 95°F)
  • Storage temperature: -40°C to +65°C (-40°F to +149°F)
  • Maximum change rate: 20°C/h (36°F/h)

Humidity (non-condensing)

  • Operating humidity: 8% RH to 90% RH
  • Storage humidity: 5% RH to 95% RH
  • Humidity change rate: < 20% RH/h

Altitude

  • Maximum altitude: 3048 m (9999.88 ft). When the altitude is higher than 900 m (2952.8 ft), the highest operating temperature decreases by 1°C (1.8°F) for every increase of 300 m (984.24 ft) in altitude.
  • HDDs are not supported at an altitude of over 3000 m (9842.5 ft).

Acoustic noise

Noise emissions are measured in accordance with ISO 7779 (ECMA 74) and declared in accordance with ISO 9296 (ECMA 109). The data listed in the following is the declared A-weighted sound power levels (LWAd) and declared average bystander position A-weighted sound pressure levels (LpAm) when the server is operating in a 23°C (73.4°F) ambient environment:

Idle:

  • LWAd: 6.2 Bels
  • LpAm: 45 dBA
NOTE:

The actual sound levels generated when the server is operating vary depending on the server configuration, workload, and ambient temperature.

Vibration

  • One cyclical sweep in each axial direction at the rate of 0.1 oct/min, a total of three axial directions.
  • 5 Hz to 10 Hz: 5 mm (0.2 in., peak-to-peak value).
  • 10 Hz to 100 Hz: 1 m/s2.

Shock

Half sine wave, peak acceleration of 2 G, 11 ms, 3 times for each surface, a total of three axial directions.

Corrosive air pollutant

  • Copper corrosion rate test requirements: The corrosion product thickness growth rate is lower than 300 Å/month (meeting level G1 requirements of the ANSI/ISA-71.04-2013 standard on gaseous corrosion).
  • Silver corrosion rate test requirements: The corrosion product thickness growth rate is lower than 200 Å/month.

Particulate pollutant

  • The equipment room environment meets the requirements of ISO 14664-1 Class 8.

    You are advised to ask a professional organization to monitor particulate pollutants in the equipment room.

  • There is no explosive, conductive, magnetic, or corrosive dust in the equipment room.

Rated input voltage

12 V DC

Maximum power

  • G560 V5: 750 W
  • GP608: 2400 W
  • GS608: 2750 W