Alarms
Alarm ID |
Alarm |
Severity |
Cause |
Impact on the System |
Measure |
---|---|---|---|---|---|
1903 |
Module overtemp. |
Major |
The temperature of the PID module is excessively high. |
The PID module does not work and generates no output. |
|
1914 |
Output overcur. |
Major |
The load current exceeds the alarm threshold. |
The PID module does not work and generates no output. The fault can be automatically rectified. |
|
1917 |
Grid volt. imbal. |
Major |
The three phases of the power grid differ greatly in voltage. |
The PID module does not work and generates no output. The fault can be automatically rectified. |
|
1918 |
Grid overvolt. |
Major |
The power grid line voltage exceeds the upper threshold. |
The PID module does not work and generates no output. The fault can be automatically rectified. |
|
1919 |
Grid undervolt. |
Major |
The power grid line voltage is lower than the lower threshold. |
The PID module does not work and generates no output. The fault can be automatically rectified. |
|
1920 |
Incorrect PV mode |
Major |
In commissioning or normal mode, running parameter settings are incorrect. |
The PID module does not work and generates no output. |
|
1921 |
Incorrect wiring |
Major |
|
The PID module does not work and generates no output. The PID module should be restarted to clear the alarm. |
|
1924 |
Grid Loss |
Major |
The power grid is power off. |
The PID module does not work. |
|
1925 |
Grid overfreq. |
Major |
The power grid frequency exceeds the upper threshold of the PID module working frequency. |
The PID module does not work. |
|
1926 |
Grid underfreq. |
Major |
The power grid frequency is lower than the lower threshold of the PID module working frequency. |
The PID module does not work. |
|
1930 |
Device fault |
Major |
The PID module is faulty. |
The PID module does not work and generates no output. |
|
1931 |
Abnormal AC-to-ground resistance |
Major |
The system AC-to-ground resistance is lower than the threshold. |
The PID module does not work. |
|