No relevant resource is found in the selected language.

This site uses cookies. By continuing to browse the site you are agreeing to our use of cookies. Read our privacy policy>Search

Reminder

To have a better experience, please upgrade your IE browser.

upgrade

X6800 Server V100R005 User Guide 01

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Replacing a Fan Module

Replacing a Fan Module

Scenario

  • A fan module is faulty.
  • A fan module needs to be repaired.

Impact on the System

Removing a fan module will make other fan modules run at full speed.

Prerequisites

  1. Matters for Attention
    • A new fan module needs to be installed properly within 2 minutes after an old one is removed, to prevent the heat dissipation performance and service processing capability of the system from being affected.
    • You can replace only one fan module at a time.
  2. Spare parts

    Obtain the spare fan module and packing materials, for example, an electrostatic discharge (ESD) bag. Place them less than 0.5 m (1.64 ft) away from the cabinet.

  3. Data

    Cabinet number and chassis number of the fan module that is to be replaced.

    Locate the fan module to be replaced in the cabinet based on the preceding information, and label its panel for identification.

  4. Tools

    ESD wrist strap or ESD gloves

Procedure

  1. Wear an ESD wrist strap or ESD gloves.
  2. Push the ejector release button fastening the ejector lever, and release the button. See (1) in Figure 5-3.
  3. Hold the ejector lever on the fan module and gently pull it out of the slot. See (2) in Figure 5-3.

    Figure 5-3 Removing a fan module

  4. Place the fan module into an ESD bag.
  5. Take a spare fan module out of an ESD bag.
  6. Hold a fan module with both hands, and insert the PSU horizontally into the slot until the fan module snaps into the chassis, as shown in Figure 5-4.

    Figure 5-4 Installing a fan module

Follow-up Procedure

Power on the chassis. The fan module is operating properly if its status indicator is steady green.

Translation
Download
Updated: 2018-08-28

Document ID: EDOC1100036738

Views: 9310

Downloads: 33

Average rating:
This Document Applies to these Products
Related Documents
Related Version
Share
Previous Next