Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Environmental Specifications

Environmental Specifications

Table 12-2 Environmental specifications

Category

Specifications

Temperature

  • Operating temperature: 5°C to 40°C (41°F to 104°F) (ASHRAE Classes A2 and A3 compliant)
  • Storage temperature: –40°C to +65°C (–40°F to +149°F)
  • Long-term storage temperature: 21°C to 27°C (69.8°F to 80.6°F)
  • Maximum temperature change rate: 20°C/h (36°F/h)
NOTE:
  • If a single fan faulty, the highest operating temperature is 5°C (41°F) lower than the rated value.
  • If the Intel® Xeon® Scalable processors (Gold 6144, 6146, 6150 or Platinum 8176, 8170) are used, the highest operating temperature is 35°C (95°F).
  • The operating temperature specifications vary depending on the processors used:
    • If the power of the processor is 165 W, the highest ambient temperature supported by the supercapacitor is 33°C (91.4°F).
    • If the power of the processor is higher than or equal to 150 W and lower than 165 W, the highest ambient temperature supported by the supercapacitor is 35°C (95°F).
    • If the power of the processor is lower than 150 W, the highest ambient temperature supported by the supercapacitor is 40°C (104°F).
  • If the server is configured with XH628 V5 and V3 nodes, the highest operating temperature is subject to the XH628 V5.

Relative humidity (RH, non-condensing)

  • Operating humidity: 5% to 85%
  • Storage humidity: 5% to 95%
  • Long-term storage humidity: 30% to 69%
  • Maximum change rate: 20%/h

Altitude

  • Operating altitude ≤ 3050 m (10006.44 ft)
    • When the server configuration complies with ASHRAE Class A2 standards and the altitude is above 900 m (2952.76 ft), the highest operating temperature decreases by 1°C (1.8°F) for every increase of 300 m (984.24 ft).
    • When the server configuration complies with ASHRAE Class A3 standards and the altitude is above 900 m (2952.76 ft), the highest operating temperature decreases by 1°C (1.8°F) for every increase of 175 m (574.14 ft).
  • HDDs cannot be used at an altitude of over 3000 m (9842.4 ft).
  • Titanium PSUs are required for the altitude higher than 3000 m (9842.4 ft).

Corrosive gaseous contaminant

Maximum corrosion product thickness growth rate:

  • Copper corrosion rate test: 300 Å/month (meeting level G1 requirements of the ANSI/ISA-71.04-2013 standard on gaseous corrosion)
  • Silver corrosion rate test: 200 Å/month

Particle contaminant

  • The equipment room environment meets the requirements of ISO 14664-1 Class 8.
  • There is no explosive, conductive, magnetic, or corrosive dust in the equipment room.
NOTE:

It is recommended that the particulate pollutants in the equipment room be monitored by a professional organization.