Site Planning Guide

OceanStor Dorado18000 V3 V300R002

This document describes the division of responsibilities between Huawei and customers during the deployment of the Dorado18000 V3 storage system and the tasks that need to be completed before the installation.
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Floor Load Capacity

Floor Load Capacity

The Dorado18000 V3 storage system can be installed on both raised floors and non-raised floors. Before installing the storage system, you must consult the specified agency to check that the storage system and associated equipment do not overweigh these floors or incur a structure risk for the building.

System Weight

Table 2-10 describes weight of components of the Dorado18000 V3 storage system. Before installing the Dorado18000 V3 storage system, consult the specified agency to ensure that the floor of an equipment room can support the Dorado18000 V3 storage system.

Table 2-10 Dimensions and weight (unpackaged)

Item

Dorado18000 V3

Dorado18000 V3 (NVMe)a

Full bay dimensions (with packages)

  • Depth: 1456 mm (57.32 in.)
  • Width: 1000 mm (39.37 in.)
  • Height: 2176 mm (85.67 in.)

Full bay dimensions (without packages)

  • Depth: 1232 mm (48.50 in.)
  • Width: 600 mm (23.62 in.)
  • Height: 2000 mm (78.74 in.)

Fully loaded weight (system bay 0 with packages)

857.3 kg (1890.02 lb)

725.7 kg (1599.89 lb)

Fully loaded weight (system bay 0 without packages)

657.3 kg (1449.10 lb)

525.7 kg (1158.97 lb)

Fully loaded weight (system bay 1 with packages)

882.8 kg (1946.24 lb)

751.2 kg (1656.11 lb)

Fully loaded weight (system bay 1 without packages)

682.8 kg (1505.32 lb)

551.2 kg (1215.19 lb)

Dimensions of a controller enclosure

  • Depth: 750 mm (29.53 in.)
  • Width: 447 mm (17.60 in.)
  • Height: 263.9 mm (10.39 in.)

Dimensions of a 2 U SAS disk enclosure

  • Depth: 488 mm (19.21 in.)
  • Width: 447 mm (17.60 in.)
  • Height: 86.1 mm (3.39 in.)

-

Dimensions of a 2 U NVMe disk enclosure (only supported in V300R002C10 and later)

  • Depth: 488 mm (19.21 in.)
  • Width: 447 mm (17.60 in.)
  • Height: 86.1 mm (3.39 in.)

PCIe switch

  • Depth: 748 mm (29.45 in.)
  • Width: 447 mm (17.60 in.)
  • Height: 43.6 mm (1.72 in.)

a: Dorado18000 V3 (NVMe) is available in V300R002C10 and later versions.

Load Capacity of a Raised Floor

For the Dorado18000 V3 storage system, raised floors are preferable to non-raised floors.

To secure the load capacity of a raised floor, use the concrete-filled steely over-loading floor whose dimensions are 600 mm (W) x 600 mm (L) as the raised floor. If using another type of floor as the raised floor, ensure that the minimum rated load of the floor is not smaller than the device weight.

Customers must ensure that the floors in an equipment room provide sufficient strength to support the storage system and associated equipment. Huawei shares no responsibility for personal injuries and device damages resulted from inadequate load capacity of these floors.

When deploying a bay on a raised floor, note the following:

  • Horizontally align the floor.
  • Ensure that the floor tiles and their vertical beams are able to bear the concentrated load of equipment room maintenance personnel and a bay's four wheels.
  • Ensure that the minimum bearing strength of a floor tile is able to bear the concentrated load of equipment room maintenance personnel and a bay.
  • Because floor tile cuts decrease the load capacity, place bases next to these cuts correctly after consulting the floor tile manufacturer.
  • You can install iron or wooden plates on the floor to reinforce it. The plates for protecting the floor are provided by carriers.
Translation
Download
Updated: 2019-07-17