Site Planning Guide

OceanStor Dorado18000 V3 V300R002

This document describes the division of responsibilities between Huawei and customers during the deployment of the Dorado18000 V3 storage system and the tasks that need to be completed before the installation.
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Power Supply Components of System Bays

Power Supply Components of System Bays

The Dorado18000 V3 storage system supports AC power and high voltage DC power. Both the North American and European standards for AC power transmission are applicable to storage systems. All bays of the storage system require the same power supply standard.

AC and High Voltage DC Scenario

Each bay of the Dorado18000 V3 storage system is equipped with two power distribution units (PDUs) on the two sides of the bay's rear end. This enables the storage system to have dual power inputs. Table 2-12 shows the number of PDUs based on each power supply mode.

Table 2-12 Number of PDUs based on each power supply mode (system bay)

Power Supply Mode

Number of PDUs

Single-phase AC: 220 V, 32 A

4

Three-phase AC: 380 V, 32 A

2

High voltage DC: 240 V, 32 A

4

North America three-phase AC: 208 V, 50 A

2

The appearances of PDUs are as follows:

Figure 2-1 Single-phase AC PDU
Figure 2-2 Three-phase AC PDU

Figure 2-3 High voltage DC PDU
Figure 2-4 North America three-phase AC PDU