Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Checking Device Specifications

Checking Device Specifications

Check device specifications before installation.

Physical Specifications

Device

Dimensions (H x W x D)

Maximum Weight

2288H V5 12-slot node

86.1 mm x 447 mm x 748 mm

34.1 kg

5288 V5 36-slot node

175 mm x 447 mm x 748 mm

65 kg

TaiShan 2280 12-slot node

86.1 mm x 447 mm x 748 mm

30 kg

TaiShan 5280 36-slot node

175 mm x 447 mm x 748 mm

57 kg

TaiShan 2280 V2 12-slot node

86.1 mm x 447 mm x 790 mm

30 kg

TaiShan 5280 V2 36-slot node

175 mm x 447 mm x 780 mm

57 kg

CE6855-48S6Q-HI

43.6 mm x 442.0 mm x 420.0 mm

8.7 kg

CE6865-48S8CQ-EI

442.0 mm x 420.0 mm x 43.6 mm

8.8 kg

CE5855-48T4S2Q-EI

43.6 mm x 442.0 mm x 420.0 mm

8.4 kg

Keyboard, Video, and Mouse (KVM)

42.5 mm x 448 mm x 601 mm

15 kg

Huawei cabinet

2000 mm x 600 mm x 1200 mm

  • 120 kg (only with the front and rear doors)
  • 170 kg (with the front door, rear door, guide rails, and cables)
NOTE:

The maximum weight refers to the weight of a storage node that is fully loaded with service disks, operating system disks, power modules, and memory modules.

Power Specifications

Device

Max. Power Consumption

Rated AC Input Voltage Scope

2288H V5 12-slot node

495 W

100 V AC to 240 V AC (50 Hz or 60 Hz)

5288 V5 36-slot node

838 W

100 V AC to 240 V AC (50 Hz or 60 Hz)

TaiShan 2280 12-slot node

432 W

100 V AC to 240 V AC (50 Hz or 60 Hz)

TaiShan 5280 36-slot node

763 W

100 V AC to 240 V AC (50 Hz or 60 Hz)

TaiShan 2280 V2 12-slot node

750 W

100 V AC to 240 V AC (50 Hz or 60 Hz)

TaiShan 5280 V2 36-slot node

1000 W

100 V AC to 240 V AC (50 Hz or 60 Hz)

CE6855-48S6Q-HI

216 W

100 V AC to 240 V AC (50 Hz or 60 Hz)

CE6865-48S8CQ-EI

470 W

100 V AC to 240 V AC (50 Hz or 60 Hz)

CE5855-48T4S2Q-EI

103 W

100 V AC to 240 V AC (50 Hz or 60 Hz)

KVM

46 W

90 V AC to 264 V AC

NOTE:

TaiShan 2280 V2 12-slot nodes and TaiShan 5280 V2 36-slot nodes are applicable to FusionStorage OBS 7.0.1 and later versions.