Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Intra-Cabinet PGND Cable

Intra-Cabinet PGND Cable

This section introduces functions, exterior, and technical specifications of an intra-cabinet PGND cable.

Function

A PGND cable is used to connect a device to the ground to protect personal and device security.

Exterior

The PGND cable has both ends equipped with OT terminals. One terminal is connected to a ground screw of a device. The other one is connected to a ground point on the mounting bar of a cabinet. Figure 14-74 shows the exterior of a PGND cable.

Figure 14-74 PGND cable

Technical Specifications

Table 14-45 describes the technical specifications of a PGND cable.

Table 14-45 Technical specifications of a PGND cable

Item

Specifications

PGND cable of a switch or KVM

  • Connector
    • Type: OT terminal
    • Maximum cross-sectional area of the cable core: 2.5 mm2
    • Bolt specifications: one terminal is M4, and the other one is M6.
  • Cable
    • Type: electronic/electrical cable
    • Conductor cross-sectional area: 2.5 mm2
    • Color: yellow and green

PGND cable of a device

  • Connector
    • Type: OT terminal
    • Maximum cross-sectional area of the cable core: 6.0 mm2
    • Bolt specifications: M6
  • Cable
    • Type: electronic/electrical cable
    • Conductor cross-sectional area: 6.0 mm2
    • Color: yellow and green