Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Meter_113104303 Meter Removal and Reinstallation of the Modular Meter

Meter_113104303 Meter Removal and Reinstallation of the Modular Meter

Description

When a meter is removed from a slot of the modular meter, this alarm is generated.

Attribute

Alarm ID Alarm Severity Alarm Type

113104303

Major

Device alarm

Impact on the System

When a meter is removed from the modular meter, the meter goes offline.

Possible Causes

  • A meter is removed from a slot of the modular meter.
  • The hardware of the modular meter fails.

Procedure

  1. Check alarm location information and confirm the information about the electrical meter on which the alarm occurs.
    1. Start the EEM, enter the user name and password, and click Go to log in to the EEM.
    2. Choose Monitoring > Alarm > Current Alarm to access the Current Alarm page and view the alarm list.
    3. Click next to the alarm. The system displays detailed information about the alarm, such as alarm location.
  2. Find the meter that generates the alarm and check whether the meter is removed from a slot of the modular meter.
    • If so, go to 3.
    • If not, go to 4.
  3. Check whether meter removal is normal.
    • If so, no action is required.
    • If not, reinstall the meter into the slot of the modular meter.
  4. Check whether the hardware of the modular meter fails.
    • If so, replace the faulty hardware.
    • If not, collect information during the troubleshooting process and contact Huawei technical support personnel.

Clearing

The alarm must be cleared manually.