NE40E V800R010C10SPC500 Installation Guide

This is NE40E V800R010C10SPC500 Installation Guide

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
NE40E-X8 DC-Input Power Cable

NE40E-X8 DC-Input Power Cable

Table 3-4 Cable and terminal specifications

Distance from the PDF to the NE40E-X8

Item

Specification

Huawei BOM Number

Remarks

Shorter than or equal to 15 m (49.21 ft.)

DC power cable

16 mm2 (6 AWG)

25030430

Blue DC power cable

25030428

Black DC power cable

OT/JG2 terminal

16 mm2 (6 AWG)–M6 double-hole JG2 naked crimping terminal

14170116

Connect to the NE40E-X8

16 mm2 (6 AWG)–M8 single-hole OT naked crimping terminal

14170024

It is connect to the PDF

Greater than 15 m (49.21 ft.) and less than 25 m (82.02 ft.)

DC power cable

25 mm2 (4 AWG)

25030101

Blue DC power cable

25030432

Black DC power cable

OT/JG2 terminal

25 mm2 (4 AWG)–M6 double-hole JG2 naked crimping terminal

14170119

It is connect to the NE40E-X8

25 mm2 (4 AWG)–M8 single-hole OT naked crimping terminal

14170060

It is connect to the PDF

Greater than 25 m (82.02 ft.) and less than 35 m (114.83 ft.)

DC power cable

35 mm2 (2 AWG)

25030199

Blue DC power cable

25030420

Black DC power cable

OT/JG2 terminal

35 mm2 (2 AWG)–M6 double-hole JG2 naked crimping terminal

14170159

It is connect to the NE40E-X8

35 mm2 (2 AWG)–M8 single-hole OT naked crimping terminal

14170063

It is connect to the PDF

Greater than 35 m (114.83 ft.)

-

A PDF or end of row needs to be placed near the NE40E-X8.

-

-

Cables and terminals

Figure 3-10 DC power cable

Figure 3-11 JG2/OT terminal

Figure 3-12 Heat-shrink tube