Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Environmental Requirements for Device Storage

Environmental Requirements for Device Storage

The environment for storing the device must comply with ETSI EN 300 019-1-1 and NEBS GR-63-CORE standards.

Climate

Table 2-1 shows the climatic requirements for device storage.

Table 2-1 Climatic requirements for device storage
Item Scope
Atmospheric pressure 70 kPa - 106 kPa
Temperature –40°C - +70°C
Temperature change rate ≤ 1°C/min
Relative humidity 5% - 100%
Solar radiation ≤ 1120 W/m2
Heat radiation ≤ 600 W/m2

Waterproof Requirements

Keep the device indoors for proper storage.

Ensure that there is no water on the floor and no water can be leaked into the packaging box. The device must be stored far away from where a water leak may occur, such as the place where the fire facility or heating equipment is located.

If a device must be stored outdoors, ensure that the following conditions are met:

  • The packaging box is intact.
  • A shelter must be provided to protect the packaging box from the rain.
  • There is no water on the floor where the packaging box is stored, and no water can be leaking into the packaging box.
  • The sun does not directly beat on the packaging box.

Biologic Environment

  • Avoid fungi, mold, and other microorganisms.
  • Prohibit rodents such as mice.

Air Cleanliness

The equipment room must be free from explosive, conductive, magnetic, and corrosive dust.

Table 2-2 shows the requirements for the concentration of mechanically active materials.

Table 2-2 Concentration of mechanically active materials
Mechanically Active Material Content
Suspending dust ≤ 5.00 mg/m3
Precipitable dust ≤ 20.0 mg/(m2·h)
Sand ≤ 300 mg/m3

Table 2-3 shows the requirements for the concentration of chemically active materials.

Table 2-3 Concentration of chemically active materials
Chemically Active Material Content
SO2 ≤ 0.30 mg/m3
H2S ≤ 0.10 mg/m3
NO2 ≤ 0.50 mg/m3
NH3 ≤ 1.00 mg/m3
Cl2 ≤ 0.10 mg/m3
HCl ≤ 0.10 mg/m3
HF ≤ 0.01 mg/m3
O3 ≤ 0.05 mg/m3

Mechanical Stress

Table 2-4 shows the requirements for mechanical stress.

Table 2-4 Mechanical stress requirements

Item

Subitem

Scope

Random vibration

Acceleration spectral density

-

0.02 m2/s3

-

Frequency

5 Hz - 20 Hz

10 Hz - 50 Hz

50 Hz - 100 Hz

dB/oct

12

-

-12