Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Installing Monitoring Serial Cables of the DACS PDB

Installing Monitoring Serial Cables of the DACS PDB

The PDB monitoring serial cable connects the DACS PDB and NE40E-X16A/NE40E-X8A chassis so that the chassis can manage the PDB.

Installation Procedures

1. Insert the RJ45 connectors of the monitoring serial cables of the PDB into the com_in interfaces on the DMU monitoring module.

NOTE:
The two monitoring serial cables must be connected to com_in 1 and com_in 2 interfaces, respectively.

2. Connect the other end of each cable to an RS485 interface of the PMU in the chassis.

The space between power cables, ground cables, and signal cables must be greater than 30 mm. Do not bundle signal cables and power cables together.

3. Use cable ties to bundle the monitoring serial cables every 150 mm (5.91 in.) and secure them to the cabinet.

Figure 15-6 PDB monitoring serial cable connection with X8A

Figure 15-7 PDB monitoring serial cable connection with X16A