Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Environmental Requirements for the Installation Site

Environmental Requirements for the Installation Site

Location

To maintain normal performance and prolong the lifespan of the NE40E, the installation site must satisfy the following environmental requirements.

The device should be installed in a standard equipment room rather than any of the locations shown in the following images.











Network box Outdoor cabinet Utility room Corridor Residential building

Environment

  • The equipment room is clean, dry, and dust-free.
  • Doors and windows are in good condition.
  • Holes in walls and ceilings for cabling are protected from rodents and dust.

Temperature and Humidity

  • Keep the NE40E's air intake and exhaust vents away from those of other devices.
  • The NE40E operating temperature ranges from 0°C to 45°C. Maintain the temperature at the air intake vent below 25°C.
  • If the equipment room has no or insufficient central air-conditioning, adding air conditioning units is essential.
  • Air conditioning units should be installed 3 meters away from a device, or with the vent facing one side of the device, to avoid blowing cold air directly on the device.
  • Equipment should not be installed in humid locations. The ambient humidity should be maintained between 5% RH and 85% RH.

Noise Control

The European Commission (EC) and U.S. Occupational Health and Safety Administration (OSHA) state that workplace noise levels should not exceed 85 dBA. If the noise level exceeds 85 dBA, hearing protection must be provided. Huawei device noise levels are lower than 78 dBA and are NEBS compliant.

The following table lists the noise control requirements for noise-sensitive areas.

Table 9-1 Noise control requirement

Level

Daytime (dBA)

Nighttime (dBA)

Area

0

50

40

Areas like rehabilitation centers and convalescent homes

1

55

45

Areas where living, medical, cultural, educational, scientific, administrative and executive activities are performed

2

60

50

Areas where commercial, financial, open market trading activities are performed, or living, commercial, and industrial activities are intermixed

3

65

55

Areas where industrial production and logistics activities are performed

4a

70

55

Areas on the sides of first and second-grade highways, urban expressways, trunk roads, distributor roads, rail transit (ground segment), and inland waterways

4b

70

60

Area on the sides of trunk railways