Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
240V/380V HVDC Power Distribution

240V/380V HVDC Power Distribution

Power Distribution Principle

NOTE:
  • One PM outputs a maximum of 3000 W power. You can configure PMs based on the required power.
  • PMs work in N+N backup mode. N PMs (N >= 1) are configured on planes A and B, respectively. The PMs are backed up in the pair of A1 and B1, A2 and B2, A3 and B3, and so on.
  • Note that different power sources must be provided for PMs on planes A and B so that one can provide power when the other becomes faulty.

Power Distribution Instance

Power Consumption

PM Configurations

3000 W

One pair of PMs, A1 and B1

6000 W

Two pairs of PMs, A1 and B1, A2 and B2

9000 W

Three pairs of PMs, A1 and B1, A2 and B2, A3 and B3

24000 W

Four pairs of PMs

Cable and Terminal Specifications

The PDF requires protection components to ensure that the rated current of each channel is not less than 16 A. The following table shows the cable and terminal specifications.

Table 8-3 Cable and terminal specifications

Huawei BOM Number

Description

04151269

Power Cable,3m,3*1.5mm^2,HVDC 3SF,227IEC53-1.5^2(3C),3*OT1-8,380V high voltage DC PEM dedicated

04151963

Power Cable,2.5m,3*1.5mm^2,HVDC 3SF,227IEC53-1.5^2(3C),PIAM,For China

04151958

Power Cable,2.5m,3*1.5mm^2,HVDC 3SF,(H05VV-F-1.5mm^2(3C)+14SJT(3C)),C20SM,PDU

NOTE:

Choose cables in the package according to standards in various countries and areas.

Installing power cables

Do not install power cables when the power is on.

  1. Install PMs.
    Figure 8-12 Installing PMs

  2. Attach temporary labels to both ends of each power cable.
  3. Route DC power cables along the cable ladder and connect them to the input terminals of the DC power distribution box. Connect the other end of each power cable to the PDF in the equipment room.
  4. After cables are inserted to the terminals, use cable fasteners to secure the cables to the terminals.
  5. Use cable ties to bundle the cables every 150 mm (5.91 in.) upwards from the bottom end, and secure the cables to the cable tray.
  6. Attach permanent labels 20 mm (0.79 in.) from both ends of each power cable.
    Figure 8-13 Installing power cables