NE40E V800R010C10SPC500 Installation Guide

This is NE40E V800R010C10SPC500 Installation Guide
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Installing a DACS PDB

Installing a DACS PDB

This section describes how to install a DACS PDB into a cabinet and install cables.

NOTE:
  • An N68E whose cabinet doors and rear boards are removed is used.
  • Cables that have proper length and are equipped with terminals are used.

Tools

Phillips screwdriver, ladder, torque meter, and marker

Related Materials

Table 15-1 Related materials

Name

Description

Quantity

Glide rail

DKBA8.038.3173,slide rail,NetEngine 5000ESubrack

2

Guide rail fixing screw

Cross Recessed Pan Head Thread forming Screws,M5*10,Zinc Electroplating, iridescent yellow,GB6560-86

8

Floating nut

Floating Nut(M6),DKBA0.480.0113

4

Panel screw

DKBA0.480.0090,Panel Screw,M6x12,For general use

4

Binding strap

Nonmetal Parts,DKBA0.480.0457-Cable Tie,150*3.6mm,White,PA66,(GT-150I)

2

PVC insulation tape

-

-

Table 15-2 External cable from the AC chassis to the DACS PDB

BOM

Description

Remarks

04001137

External Cable Suite,NE40E,C19 PDU Power Cords All Over The World

Each power module is configured with one.

04050422

Power Cords Cable,China /Europe/America/Korea Multiple Certificate AC Power 250V16A,3.0m,C20SM,H05VV-F-1.5mm^2(3C) +14SJT3(3C),C19SF,PDU Cable

04050856

Power Cords Cable,Australia AC Power 250V16A,3.0m,C20SM,H05VV-F-1.5^2(3C),C19SF,PDU Power Cord

04050855

Power Cords Cable,Japan AC Power 250V15A,3.0m,C20SM,VCTF-2.0^2(3C),C19SF,PDU Power Cord

04050785-001

Power cord,China AC Power 250V16A,3m,C20 SM,227IEC53-1.5^2(3C),C19 SF,250V,16A,Yellow

25030431

Electronic|Electric Cable,450V/750V,60227 IEC 02(RV),25mm^2,Yellow/Green,112A,CCC,CE

Each device is configured with one. The cable length depends on the site survey. If the device is grounded through a cabinet, the cable length refers to the length from the device to the ground point of the cabinet, which defaults to 3 m. If the device is directly grounded, the cable length refers to the length from the device to the ground bar, which defaults to 25 m.

02230FQE

Accessories,NE40E&80E,Package of Terminal for Single Input 25mm^2 DC Power Cable or Grounding Cable(Exclude Backup)

  • Each chassis is configured with one.
  • If power cables are separately purchased by the customer, the terminal package is not delivered by default.
Table 15-3 Input cables from the power distribution panel to the DACS PDB and terminals for the cables

Length in Site Survey

BOM

Description

Remarks

The length of a single cable is less than 50 m in a three-phase 32 A input non-short-circuit scenario.

25030893

Electronic|Electric Cable,600V/1000V,ZA-YJV,5x10mm^2,Black(5Cores:Yellow,Green,Red,Blue,Black),80A,CE

This type of cable is used in three-phase 32 A input scenarios. It is delivered by default. Each AC PDB is configured with four such cables. The cable length depends on the site survey.

02232QKB

MPE Site Materials Kit,DACS, Package of Terminal for 10mm^2 AC Input Power Cable(Include Backup)

  • This type of terminal package is used in three-phase 32 A input scenarios. It is delivered by default. Each AC PDB is configured with one such package.
  • If power cables are separately purchased by the customer, the terminal package is not delivered by default.

25030429

Electronic|Electric Cable,450V/750V,60227 IEC 02(RV),16mm^2,Yellow/Green,85A,CCC,CE

Each device is configured with one. The cable length depends on the site survey. If the PDB is grounded through a cabinet, the cable length refers to the length from the device to the ground point of the cabinet, which defaults to 3 m. If the PDB is directly grounded, the cable length refers to the length from the device to the ground bar, which defaults to 25 m.

02232QFU

MPE Site Materials Kit,Package of Terminal for 16mm^2 DC Power Cable/PGND Cable of NE40E X8A/X16A (Exclude Backup)

  • Each AC PDB is configured with one such package.
  • If power cables are separately purchased by the customer, the terminal package is not delivered by default.

The length of a single cable is less than 50 m in a three-phase 63 A input short-circuit scenario.

25030857

Electronic|Electric Cable,600V/1000V,ZA-YJV,5x16mm^2,Black(5Cores:Yellow,Green,Red,Blue,Black),96A

This type of cable is used in three-phase 63 A input scenarios. Each AC PDB is configured with two such cables. The cable length depends on the site survey.

02232QKC

MPE Site Materials Kit,DACS, Package of Terminal for 16mm^2 AC Input Power Cable(Include Backup)

  • This type of terminal package is used in three-phase 63 A input scenarios. It is delivered by default. Each AC PDB is configured with one such package.
  • If power cables are separately purchased by the customer, the terminal package is not delivered by default.

25030429

Electronic|Electric Cable,450V/750V,60227 IEC 02(RV),16mm^2,Yellow/Green,85A,CCC,CE

Each device is configured with one. The cable length depends on the site survey. If the PDB is grounded through a cabinet, the cable length refers to the length from the device to the ground point of the cabinet, which defaults to 3 m. If the PDB is directly grounded, the cable length refers to the length from the device to the ground bar, which defaults to 25 m.

02232QFU

MPE Site Materials Kit,Package of Terminal for 16mm^2 DC Power Cable/PGND Cable of NE40E X8A/X16A (Exclude Backup)

  • Each AC PDB is configured with one such package.
  • If power cables are separately purchased by the customer, the terminal package is not delivered by default.

The length of a single cable is less than 15 m in a single-phase 63 A input short-circuit scenario.

25031887

Electronic|Electric Cable,600V/1000V,ZA-RVV,3x16mm^2,Black(3Cores:Brown,Blue,Yellow/Green),76A,Outdoor Cable,CE

This type of cable is used in single-phase 63 A input scenarios. Each AC PDB is configured with four such cables. The cable length depends on the site survey.

02232QKC

MPE Site Materials Kit,DACS, Package of Terminal for 16mm^2 AC Input Power Cable(Include Backup)

  • This type of terminal package is used in single-phase 63 A input scenarios. It is delivered by default. Each AC PDB is configured with one such package.
  • If power cables are separately purchased by the customer, the terminal package is not delivered by default.

25030431

Electronic|Electric Cable,450V/750V,60227 IEC 02(RV),25mm^2,Yellow/Green,112A,CCC,CE

Each device is configured with one. The cable length depends on the site survey. If the PDB is grounded through a cabinet, the cable length refers to the length from the device to the ground point of the cabinet, which defaults to 3 m. If the PDB is directly grounded, the cable length refers to the length from the device to the ground bar, which defaults to 25 m.

02232QFU

MPE Site Materials Kit,Package of Terminal for 16mm^2 DC Power Cable/PGND Cable of NE40E X8A/X16A (Exclude Backup)

  • Each AC PDB is configured with one such package.
  • If power cables are separately purchased by the customer, the terminal package is not delivered by default.

Installation Procedures

  1. Install guide rails and floating nuts, as shown in Figure 15-1.
    • Install two guide rails 4 U below the top of the PDB and align the bottom of guide rails with the corresponding scale line. Eight M5x10 cross recessed pan head thread forming screws are required.
    • Install two M6 floating nuts into the 8th and 12th holes from the bottom of the guide rail.
    Figure 15-1 Installing guide rails and floating nuts

  2. Connect the single-hole end of the ground cable to the column of the cabinet using the M6x16 cross recessed pan head screws, as shown in Figure 15-2.
    Figure 15-2 Installing one end of the ground cable

  3. Install the PDB into the cabinet.

    Hold the flexible PDB from the back when carrying it and push it into the cabinet along the guide rails. Use four M6x12 panel screws to secure the PDB and the cabinet.

    NOTE:
    The PDB is heavy and needs to be carried by 2 to 3 people. Avoid stepping on the air filter at the bottom of the cabinet.
    Figure 15-3 Installing the PDB into the cabinet

  4. Route the ground cables and secure the ground cables to the ground point of the PDB, as shown in Figure 15-4. Bundle ground cables.
    Figure 15-4 Installing the other end of the ground cable

  5. Install the power module.

    Hold the handle of an AC power module with one hand, and the middle of the power module with the other hand. Install the power module from the back of the chassis. Filler panels must be installed in the slots without power modules. For details about the mappings between the slot IDs of AC/AC power modules and the IDs of PEM wiring terminal, see the mappings between inputs and outputs previously described.



    Keep the TOP side of the AC power module upwards during installation and ensure that the installation position of the AC power module matches the PEM wiring position of the PDB.
Translation