NE40E V800R010C10SPC500 Installation Guide

This is NE40E V800R010C10SPC500 Installation Guide
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
DC Power Distribution

DC Power Distribution

Power Distribution Principle

NOTE:
  • One PM outputs a maximum of 2200 W power. You can configure PMs based on the required power.
  • PMs work in N+1 (N >= 1) backup mode. Each PM uses two channels of power inputs with different power sources, in the backup form of A1 and B1, A2 and B2, and so on.
  • Note that different power sources must be provided for PMs on planes A and B so that one can provide power when the other becomes faulty.
  • To facilitate further expansion, configure the PMs and install power cables in ascending order of PM slot numbers.

Power Distribution Instance

You can configure PMs based on the power consumption.

Power Consumption

PM Configurations

2200 W

1+1 PMs

4400 W

2+1 PMs

6600 W

3+1 PMs

......

......

33000 W

15+1 PMs

Cable and Terminal Specifications

The PDF requires protection components to ensure that the rated current of each channel is not less than 63 A. The following table shows the cable and terminal specifications.

Table 8-2 Cable and terminal specifications

Distance from the PDF to the NE40E-X16A

Item

Specification

Huawei BOM Number

Remarks

Shorter than or equal to 25 m (82.02 ft.)

DC power cable

25 mm2 (4 AWG)

25030101

Blue

25030432

Black

OT terminal

25 mm2 (4 AWG)–M6 double-hole OT2 naked crimping terminal

14170119

It is connected to the device.

25 mm2 (4 AWG)–M8 single-hole OT naked crimping terminal

14170060

It is connected to the PDF.

Heat-shrink tube

Heat-Shrink Tube, D14, Radial Shrinkage Ratio>50%,Black

28040009

-

Greater than 25 m (82.02 ft.) and less than 35 m (114.83 ft.)

DC power cable

35mm2 (2 AWG)

25030199

Blue

25030420

Black

OT terminal

35 mm2 (2 AWG)–M6 double-hole OT2 naked crimping terminal

14170159

It is connected to the device.

35 mm2 (2 AWG)–M8 single-hole OT naked crimping terminal

14170063

It is connected to the PDF.

Heat-shrink tube

Heat-Shrink Tube, D18, Radial Shrinkage Ratio>50%,Black

28040013

-

Greater than 35 m (114.83 ft.)

-

A PDF or end of row needs to be placed near the NE40E-X16A.

-

-

Installing DC PMs and Power Cables

Do not install power cables when the power is on.

  1. Install DC PMs.
    Figure 8-10 Installing DC PMs

  2. Route power cables along the cable ladder to the chassis.
  3. Remove plastic covers on connection boxes of power modules.
  4. Connect one end of each power cable to the corresponding terminal and the other end to the PDF.
  5. After connecting power cables, restore the plastic covers to their original positions.
  6. Use cable ties to bundle the cables every 150 mm (5.91 in.) upwards from the bottom and secure the cables to the vertical cable trough.
  7. Attach permanent labels 20 mm (0.79 in.) to both ends of each ground cable.
    Figure 8-11 Installing power cables

NOTE:

If the NE40E-X16A is installed in an N68E cabinet, route power cables downwards, as shown in the following figure.

NOTE:

To ensure that the power cable is an appropriate length, perform the following steps:

  1. Prepare a power cable with a length longer than the distance between the power module and PDF.
  2. Install a terminal on one end of the power cable and connect the terminal to the device.
  3. Route the power cable, bind it to the vertical cable trough, and route it to the PDF. Cut any excess length from the cable. Install a terminal on the other end of the power cable and connect the terminal to the PDF.
Translation