Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Air Cleanliness Requirements

Air Cleanliness Requirements

The equipment room must be free from explosive, conductive, magnetic, and corrosive dust.

Table 2-12 shows the requirements for the concentration of mechanically active materials.

Table 2-12 Concentration of mechanically active materials

Mechanically Active Material

Unit

Content

Suspending dust

mg/m3

≤ 0.4

Precipitable dust

mg/m2·h

≤ 15

Sand

mg/m3

≤ 300

Table 2-13 shows the requirements for the concentration of chemically active materials.

Table 2-13 Concentration of chemically active materials
Chemically Active Material Content
SO2 ≤ 0.30 mg/m3
H2S ≤ 0.10 mg/m3
NH3 ≤ 1.00 mg/m3
Cl2 ≤ 0.10 mg/m3
HCl ≤ 0.10 mg/m3
HF ≤ 0.01 mg/m3
O3 ≤ 0.05 mg/m3
NOX ≤ 0.50 mg/m3