No relevant resource is found in the selected language.

This site uses cookies. By continuing to browse the site you are agreeing to our use of cookies. Read our privacy policy>Search

Reminder

To have a better experience, please upgrade your IE browser.

upgrade

NE40E-M2 V800R010C10SPC500 Installation Guide

This is NE40E-M2 V800R010C10SPC500 Installation Guide
Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Requirements for Temperature, Humidity, and Altitude

Requirements for Temperature, Humidity, and Altitude

Proper temperature, humidity, and altitude must be ensured for the equipment room. Table 2-2 lists the specific requirements.
Table 2-2 Requirements for temperature, humidity, and altitude

Item

Requirements

Temperature

Long-term operation

-5°C to 65°C (DC)

Short-term operation

-5°C to 65°C (DC)

The short term in the preceding table refers to a maximum of 96 consecutive working hours or a maximum of 15 cumulative working days each year.

Storage temperature

-40°C (-40°F) to +70°C (158°F)

Relative humidity

Long-term operation

5% RH to 85% RH, non-condensing

Short-term operation

5% RH to 95% RH, non-condensing

Storage relative humidity

0% RH to 95% RH, non-condensing

Long-term operation altitude

Less than 3,000 m (9842.4 ft)

Storage altitude

Less than 5,000 m (16404 ft)

NOTE:
  • The measurement point of the temperature and humidity is 1.5 m (4.92 ft) above the floor and 0.4 m (1.31 ft) from the front of a cabinet. Before measuring temperature and humidity, remove the protection panels at the front or back of the cabinet.
  • Short-term operation means that the continuous working time does not exceed 96 hours and the accumulated time per year does not exceed 15 days.
Take the following measures to ensure that the preceding requirements can be met:
  • Use a temperature-control device no matter what the local climate is.
  • In areas with low humidity, use a humidifier or regularly mop the ground with water.
  • In areas with high humidity, use a dehumidifier.