Hardware Description

NE05E and NE08E V300R003C10SPC500

This is NE05E and NE08E V300R003C10SPC500 Hardware Description
Rate and give feedback :
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
ETP4830-B1A2 Power System

ETP4830-B1A2 Power System

The ETP4830-B1A2 external power system converts input 220 V AC power to -53.5 V DC power and supplies power to the NE.

Appearance

Figure 7-12 shows the appearance and structure of an ETP4830-B1A2.

Figure 7-12 Appearance of an ETP4830-B1A2

Indicators

Indicators for the rectifier and monitoring modules are present on the front panel of the ETP4830-B1A2. Table 7-14 lists the indications of indicators for the rectifier modules respectively.

Table 7-14 Indicators for the rectifier modules

Indicator

Color

Status

Description

Power indicator

Green

Steady on

The rectifier has an AC power input.

Off

The rectifier has no AC power input.

The rectifier is faulty.

Alarm indicator

Yellow

Blinking

No alarm is generated.

Steady on

The rectifier generates an alarm for power limiting due to ambient overtemperature.

The rectifier generates an alarm for shutdown due to ambient overtemperature or undertemperature.

The rectifier protects against AC input overvoltage or undervoltage.

The rectifier is hibernating.

Fault indicator

Red

Off

The rectifier is running properly.

Steady on

The rectifier locks out due to output overvoltage.

The rectifier has no output due to an internal fault.

Interfaces and Air breakers

Table 7-15 lists types and usage of the interfaces and air breakers on the front panel of the ETP4830-B1A2. Figure 7-13 shows the relationships of the AC input interfaces, load output interfaces, and air breakers.

Table 7-15 Interfaces and air breakers on the front panel of the ETP4830-B1A2

Interface Name

Number of Interfaces

Type

Description

Remarks

AC INPUT1

1

Interface

220 V AC power input interface

-

AC INPUT2

1

Interface

220 V AC power input interface

-

LOAD1

1

Air breaker

Air breaker for load 1

-

LOAD2

1

Air breaker

Air breaker for load 2

-

LOAD1

1

Interface

Output interface for load 1

LOAD1 and LOAD2 provide DC power for two PIUs. For how to connect the load interfaces to the PIUs.

LOAD2

1

Interface

Output interface for load 2

Figure 7-13 Relationships of the AC input interfaces, load output interfaces, and air breakers

Technical Specifications

Table 7-16 lists the technical specifications of the ETP4830-B1A2.

Table 7-16 Technical specifications of the ETP4830-B1A2

Item

Specifications

Dimensions (H x W x D)

43.6 mm x 442 mm x 255 mm

Weight

≤10 kg (with rectifiers)

AC input

Input lines

2

Rated voltage

110 V AC or 220 V AC

Voltage range

  • 100-120 V AC
  • 200-240 V AC

Maximum current

4.9 A

DC output

Output lines

2

Default output voltage

-53.5 V DC

Maximum current

  • 8.6 A (100-120 V AC)
  • 12 A (200-240 V AC)

Environmental conditions

-40ºC to +65ºC