This document of the NIP6800 Series describes hardware structure, installation guide, and hardware maintenance. The content of this document includes the appearance and specifications of the product, the supported expansion cards, preparation before the installation, installation, cabling, and hardware replacement.
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Preparing the Site

Preparing the Site

Prior to device installation, deploy the cabinet and device according to the following power supply, cabinet, cabinet clearance, and device clearance requirements to ensure that the device works properly.

Power Supply System Requirements

  • If DC power supply is used, ensure that the outputs of the DC power distribution box fall between -72 V DC and -38 V DC. Two power modules are needed, and each power module must be connected to two different power sources for redundancy.
  • If AC power supply is used, ensure that the output voltage of the AC power distribution cabinet falls between 90 V AC and 175 V AC (with rated input voltage being 110 V) or between 175 V AC and 264 V AC (with rated input voltage being 220 V) and that two groups of power modules are provided for redundancy.

    With the 110 V AC power supply, the NIP6830 must use 110 V dual-live-wire AC input to meet the maximum system power consumption with the full configuration. This is because AC power modules are half-load output with 110 V AC input, which cannot meet the system power consumption.

Cabinet Requirements

You are advised to use Huawei standard NE68E cabinet. Any other cabinet must meet Requirements for Customers' Cabinets Purchased from Other Vendors.

Cabinet Clearance Requirements

The N68E-22 cabinet is used as an example. As shown in Figure 2-5, cabinet clearance must meet the following requirements:

  • Aisles in the equipment room ≥ 1000 mm; aisles between cabinet rows ≥ 1000 mm
  • Space between cabinet sides and wall ≥800 mm
  • Space between cabinet row and wall ≥ 1000 mm
Figure 2-5  Diagram for cabinet deployment

Device Clearance Requirements

The NIP6830 DC chassis is 4 U high, and the NIP6830 AC chassis is 5 U. The NIP6830 requires front and back maintenance mode. The device must meet the following clearance requirements:

  • Airflow

    • A minimum of 75 mm between the air intake of the cabinet and neighboring objects. If the air intake of the cabinet is next to another communication device, a minimum of 150 mm is required
    • A minimum of 2 U between devices installed in the same cabinet, between the top-most device and the cabinet top, and between the bottom-most device and the cabinet bottom
  • Maintenance

    A minimum of 350 mm between the rear of the cabinet and neighboring objects

NOTE:

The length of three holes on the mounting rails is 1 U, which is equivalent to 44.45 mm.