This document of the NIP6800 Series describes hardware structure, installation guide, and hardware maintenance. The content of this document includes the appearance and specifications of the product, the supported expansion cards, preparation before the installation, installation, cabling, and hardware replacement.

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
NIP6860 Power Distribution Design Guide

NIP6860 Power Distribution Design Guide

This section describes how to configure power distribution for the NIP6860.

DC Power Distribution Guide

This section describes how to select DC power distribution cables and circuit breakers of the DC PDF.

Figure 2-46 shows the DC PEMB.

Figure 2-46  DC PEMB

Table 2-12 lists the current parameters of each circuit breaker and each power line for the PDF

Table 2-12  Current parameters of circuit breakers and power lines for the PDF (DC PEMB)

Item

Specification

Note

Each circuit breaker (A1,A2,B1,B2)

≥ 60 A

To protect power supplies of different levels, it is recommended that the current of the circuit breaker on the user side be greater than or equal to that of the circuit breaker of the power module (70 A).

Each power supply (A1,A2,B1,B2)

≥60 A

To support the maximum configuration, it is recommended that each DC power line should provide a minimum of 60 A current.

If the PDF cannot provide 70 A circuit breakers and full configuration is unnecessary, select the circuit breaker of each DC line using the following formula (A1,A2,B1,B2).

I = P / (Vin * D * 2)

I: rated current of the circuit breaker of each line on the PDF, in Ampere (A).

P: total power of each device.

Vin: input voltage of the power supply. (38 < Vin < 72)

D: derating coefficient. The recommended coefficient is 0.8.

2: number of the input lines of power module.

Table 2-13 describes how to select power cables (a1,a2,b1,b2)

Table 2-13  Cables for the PEMB

Distance from the PDF to the Device

Power Cables a and b

Shorter than or equal to 15 m

Wire,450/750V,227 IEC 02(RV)16mm2,blue,85A

Each power module should be equipped with one cable of this type. The cable length is determined by an onsite project survey.

Wire,450/750V,227 IEC 02(RV)16mm2,black,85A

Each power module should be equipped with one cable of this type. The cable length is determined by an onsite project survey.

Naked Crimping Terminal,JG2,16mm2,M6,95A,Tin Plated,for OEM

Each cable should be equipped with one terminal of this type.

Naked Crimping Terminal,OT,16mm2,M8,Tin Plating,Naked Ring Terminal

Each cable should be equipped with one terminal of this type.

Longer than 15 m or shorter than or equal to 25 m

Wire,450/750V,227 IEC 02(RV)25mm2,blue,110A

Each power module should be equipped with one cable of this type. The cable length is determined by an onsite project survey.

Wire,450/750V,227 IEC 02(RV)25mm2,black,110A

Each power module should be equipped with one cable of this type. The cable length is determined by an onsite project survey.

Naked Crimping Connector,JG2,25mm2,M6,150A,Tin Plating,For OEM

Each cable should be equipped with one terminal of this type.

Naked Crimping Terminal,OT,25mm2,M8,Tin Plating,Naked Ring Terminal

Each cable should be equipped with one terminal of this type.

Longer than 25 m or shorter than or equal to 35 m

Wire,450/750V,227 IEC 02(RV)35mm2,Blue,135A

Each power module should be equipped with one cable of this type. The cable length is determined by an onsite project survey.

Wire,450/750V,227 IEC 02(RV)35mm2,black,135A

Each power module should be equipped with one cable of this type. The cable length is determined by an onsite project survey.

Naked Crimping Connector,JG2,34.3mm2,M6(1/4"),134A,Tin Plated,2AWG,Hole Center Distance 15.875mm(5/8"),Short Tube,for North American

Each cable should be equipped with one terminal of this type.

Naked Crimping Terminal,OT,35mm2,M8,Tin Plating,Naked Ring Terminal

Each cable should be equipped with one terminal of this type.

Longer than 35 m

A PDF should be placed near the device.

Formula for calculating cable cross-sectional area

S = ( I * L ) / 74

S: cross-sectional area

I: the current flowing through the cable

L: distance from the PDF to the device

AC Power Distribution Guide

This section describes AC power distribution and AC cable matchings.

NOTE:

If the customer uses a purchased three-core cable, the ground core does not need to be connected to the ground terminal on the device. This is because the ground terminal on the device has already been connected to a separate ground cable, ensuring that the device is properly grounded.

Figure 2-47 shows the AC power module. AC power input is converted into regulated DC power through an AC/DC converter. The resulting DC power output is connected to the PEMs through external cables to supply power to all boards and fan modules.

Figure 2-47  AC power distribution

NOTE:

It is recommended that the current specifications of the circuit breakers on the PDF or distribution box be no less than 16 A

Table 2-14 lists the cables and terminals for the EPS200-4850A AC power chassis.

Table 2-14  Cables and terminals for the EPS200-4850A AC power chassis

Item

Description

a1,b1,c1,d1

Power cable

Power Cable,300/500V,60227IEC10(BVV),6mm2,Black Jacket(Cores:Blue,Brown),43A,2 Equivalent Cores

Terminal

Naked Crimping Terminal,OT,6mm2,M6,Tin Plating,Insulated Ring Terminal,12~10AWG,yellow

Naked Crimping Terminal,OT,6mm2,M8,Tin Plating,Insulated Ring Terminal,12~10AWG,yellow

a2,b2,c2,d2

Cables

Wire,450/750V,227 IEC 02(RV)16mm2,blue,85A

Wire,450/750V,227 IEC 02(RV)16mm2,black,85A

Terminal

Naked Crimping Terminal,JG2,16mm2,M6,95A,Tin Plated,for OEM

Table 2-15 lists the cables and terminals for the EPS200-4850B AC power chassis.

Table 2-15  Cables and terminals for the EPS200-4850B AC power chassis

Item

Description

a1,b1,c1,d1

Power cable

External Suite, Power Cords All Over The World, Class I Equipment With Connector C19, External Cable Set

a2,b2,c2,d2

Cables

Wire,450/750V,227 IEC 02(RV)16mm2,blue,85A

Wire,450/750V,227 IEC 02(RV)16mm2,black,85A

Terminal

Naked Crimping Terminal,JG2,16mm2,M6,95A,Tin Plated,for OEM