This document of the NIP6800 Series describes hardware structure, installation guide, and hardware maintenance. The content of this document includes the appearance and specifications of the product, the supported expansion cards, preparation before the installation, installation, cabling, and hardware replacement.
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Construction Requirements for the Equipment Room

Construction Requirements for the Equipment Room

Table 4-9 describes the construction requirements for the equipment room.
Table 4-9  Construction requirements for the equipment room

Item

Requirements

Area

The smallest area of the equipment room can accommodate the equipment with the largest capacity.

Net height

The minimum height of the equipment room indicates the net height below the beam or the ventilation pipe. The minimum height of the equipment room is 3 m.

Floor

The floor in the equipment room should be semi-conductive and dustproof. A raised floor with an ESD function is recommended. Pave the floor solidly and evenly. The horizontal tolerance of each square meter should be less than 2 mm. If a raised floor is not possible, use floor material that conducts static electricity, with a volume resistivity of 1.0 x 107 ohms to 1.0 x 1010 ohms. Ground the floor material that conducts static electricity or raise the floor so that static electricity can be conducted. You can connect them with the grounding unit by using the current limiting resistor and connection line. The resistance of the current limiting resistor is one megohm.

Load-bearing capacity

Larger than 150 kg/m2.

Door and windows

The door of the equipment room should be 2 m high and 1 m wide. One door is sufficient. Install doors and windows with dustproof plastic tape to maintain a seal. Install double-layer windows and seal them.

Wall surface treatment

Install wallpaper or apply flat paint to the wall surface. Do not use pulverized paint.

Grooves

Use grooves to arrange cables. The inner faces of the grooves must be smooth. The reserved length and width of the grooves and the number, position, and dimensions of the holes must comply with the requirements of device arrangement.

Water pipe

Do not pass service pipes, drainpipes, or storm sewers through the equipment room. Do not install a fire hydrant in the equipment room. A fire hydrant can be installed in a hall or near a staircase.

Internal partition wall

Divide the equipment and the door using an internal partition wall. This prevents intrusion of dust.

Installation position of the air conditioner

Install the air conditioner in a suitable location so that it does not blow air directly onto the device.

Other

Protect the equipment room from mildew and rodents.

Figure 4-43  Internal partition wall inside the equipment room