This document of the NIP6800 Series describes hardware structure, installation guide, and hardware maintenance. The content of this document includes the appearance and specifications of the product, the supported expansion cards, preparation before the installation, installation, cabling, and hardware replacement.
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
DC Power Cable

DC Power Cable

This section describes the DC power cables of the NIP6800 with DC power supply. Learn about the structure and specifications of the DC power cable before you make or purchase any power cables for the NIP6800.

DC Power Cable of the NIP6830

This section describes the DC power cable of the NIP6830.

Structure and Appearance

The DC power cable consists of a -48 V power cable NEG(-), and a cable RTN (+). The power cable transfers -48 V DC from the DC distribution equipment to the terminal block of the NIP6800 power module, supplying power for the NIP6800.

The DC power cables of the NIP6800 are delivered in an integrated way. Cut the power cables to adjust them according to site requirements. Figure 1-52 and Figure 1-53 show the two power cables.

Figure 1-52  NEG(-)

Figure 1-53  RTN (+)

DC cable terminals vary based on the device. Two commonly used terminals are the OT terminal and the JG2 double-hole terminal.

terminals must be crimped on both ends of the power cable.

Figure 1-54 shows the OT terminal without a cable.

Figure 1-54  OT terminal

Figure 1-55 shows the JG2 double-hole terminal without a cable.

Figure 1-55  JG2 double-hole terminal

If the power supply distance is longer than 35 m, you must place the DC power distribution cabinet closer to the NIP6800.

Prepare cables according to the distance between the NIP6800and the power distribution cabinet.

Power Supply Distance Shorter Than or Equal to 15 m

If the power supply distance is shorter than or equal to 15 m, use the 16 mm2 power cable to connect the NIP and the DC power distribution cabinet.Table 1-87 lists the cable terminals and cable types.

Table 1-87  Cable for power supply distance shorter than or equal to 15 m

Item

Description

Cable type

NEG power cable (-48 V)

Wire,450/750V,60227 IEC 02(RV)16mm2,blue,85A

RTN power cable

Wire,450/750V,60227 IEC 02(RV)16mm2,black,85A

Terminal

NIP6830

Naked Crimping Terminal,JG2,16mm2,M6,95A,Tin Plated,for OEM

DC power distribution cabinet

Naked Crimping Terminal,OT,16mm2,M8,Tin Plating,Naked Ring Terminal

Power Supply Distance Longer Than 15 m or Shorter Than or Equal to 35 m

If the power supply distance is longer than 15 m or shorter than or equal to 35 m, use the 25 mm2 power cable to connect in the NIP6830 and the DC power distribution cabinet. Table 1-88 lists the cable terminals and cable types.

Table 1-88  Cables for power supply distance longer than 15 m or shorter than or equal to 35m

Item

Description

Cable type

NEG power cable (-48 V)

Wire,450/750V,227 IEC 02(RV)25mm2,blue,110A

RTN power cable

Wire,450/750V,227 IEC 02(RV)25mm2,black,110A

Terminal

NIP6830

Naked Crimping Connector,JG2,25mm2,M6,150A,Tin Plating,For OEM

DC power distribution cabinet

Naked Crimping Terminal,OT,25mm2,M8,Tin Plating,Naked Ring Terminal

DC Power Cable of the NIP6860

This section describes the DC power cable of the NIP6860.

DC power cable uses as:

  • DC-input power cable.
  • The cable between the AC power chassis and the device.
Structure and Appearance

The DC power cable consists of a -48 V power cable NEG(-), and a cable RTN (+). The power cable transfers -48 V DC from the DC distribution equipment to the terminal block of the NIP6800 power module, supplying power for the NIP6800.

The DC power cables of the NIP6800 are delivered in an integrated way. Cut the power cables to adjust them according to site requirements. Figure 1-56 and Figure 1-57 show the two power cables.

Figure 1-56  NEG(-)

Figure 1-57  RTN (+)

DC cable terminals vary based on the device. Two commonly used terminals are the OT terminal and the JG2 double-hole terminal.

terminals must be crimped on both ends of the power cable.

Figure 1-58 shows the OT terminal without a cable.

Figure 1-58  OT terminal

Figure 1-59 shows the JG2 double-hole terminal without a cable.

Figure 1-59  JG2 double-hole terminal

If the power supply distance is longer than 35 m, you must place the DC power distribution cabinet closer to the NIP6800.

Prepare cables according to the distance between the NIP6800and the power distribution cabinet.

Power Supply Distance Shorter Than 3 m (Cables Between the AC power chassis and the NIP6860)

Place the AC power chassis as close to the device as possible. If the distance is shorter than or equal to 3 m, use the cabling scheme described in Table 1-89.

Table 1-89  Cable types and terminals of the AC-input power cable

Item

Description

Cable Type

NEG power cable (-48 V)

Wire,450/750V,60227 IEC 02(RV)16mm2,blue,85A

RTN power cable

Wire,450/750V,60227 IEC 02(RV)16mm2,black,85A

Terminal

NIP6860

Naked Crimping Terminal,JG2,16mm2,M6,95A,Tin Plated,for OEM

Power Supply Distance Shorter Than or Equal to 15 m

If the power supply distance is shorter than or equal to 15 m, use the 16 mm2 power cable to connect the NIP6860 and the power distribution cabinet. Table 1-90 lists the cable terminals and cable types.

Table 1-90  Cables for power supply distance shorter than or equal to 15 m

Item

Description

Cable type

NEG power cable (-48 V)

Wire,450/750V,60227 IEC 02(RV)16mm2,blue,85A

RTN power cable

Wire,450/750V,60227 IEC 02(RV)16mm2,black,85A

Terminal

NIP6860

Naked Crimping Terminal,JG2,16mm2,M6,95A,Tin Plated,for OEM

DC power distribution cabinet

Naked Crimping Terminal,OT,16mm2,M8,Tin Plating,Naked Ring Terminal

Power Supply Distance Longer Than 15 m or Shorter Than or Equal to 25 m

If the power supply distance is longer than 15 m or shorter than or equal to 25 m, use the 25 mm2 power cable to connect the NIP6860 to the power distribution cabinet. Table 1-91 lists the cable terminals and cable types.

Table 1-91  Cables for power supply distance longer than 15 m or shorter than or equal to 25 m

Item

Description

Cable type

NEG power cable (-48 V)

Wire,450/750V,227 IEC 02(RV)25mm2,blue,110A

RTN power cable

Wire,450/750V,227 IEC 02(RV)25mm2,black,110A

Terminal

NIP6860

Naked Crimping Connector,JG2,25mm2,M6,150A,Tin Plating,For OEM

DC power distribution cabinet

Naked Crimping Terminal,OT,25mm2,M8,Tin Plating,Naked Ring Terminal

Power Supply Distance Longer Than 25 m or Shorter Than or Equal to 35 m

If the power supply distance is longer than 25 m or shorter than or equal to 35 m, use the 35 mm2 power cable to connect the NIP6860 and the power distribution cabinet. Table 1-92 lists the cable terminals and cable types.

Table 1-92  Cables for power supply distance longer than 25 m or shorter than or equal to 35 m

Item

Description

Cable type

NEG power cable (-48 V)

Wire,450/750V,60227 IEC 02(RV)35mm2,Blue,135A

RTN power cable

Wire,450/750V,60227 IEC 02(RV)35mm2,black,135A

Terminal

NIP6860

Naked Crimping Connector,JG2,34.3mm2,M6(1/4"),134A,Tin Plated,2AWG,Hole Center Distance 15.875mm(5/8"),Short Tube,for North American

DC power distribution cabinet

Naked Crimping Terminal,OT,35mm2,M8,Tin Plating,Naked Ring Terminal