This document of the NIP6800 Series describes hardware structure, installation guide, and hardware maintenance. The content of this document includes the appearance and specifications of the product, the supported expansion cards, preparation before the installation, installation, cabling, and hardware replacement.

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Requirements for Customers' Cabinets Purchased from Other Vendors

Requirements for Customers' Cabinets Purchased from Other Vendors

This section describes the requirements on customers' cabinets purchased from other vendors.

Cabinets purchased from other vendors must meet the following requirements:

  • The rack mounting rail is positioned more than 150 mm from the front door of the cabinet, and the front door is less than 25 mm thick, ensuring that the available space is at least 125 mm.

    Figure 4-60  Rack mounting rail requirements

  • Customized cabinets must be 19-inch standard cabinets with a depth of more than 800 mm and 465 mm of space between the installation holes on the two rack mounting rails.

    Figure 4-61  Customized cabinet requirements

  • If overhead cabling is used, a cable outlet must be reserved on the top of the cabinet; if underfloor cabling is used, a cable outlet must be reserved in the bottom of the cabinet.

  • The cabinets contain installation accessories such as slide rails, captive nuts, and screws.
  • The cabinets contain ground points. If the ground point is reserved, connect the device to the ground point and connect the ground point to the ground busbar. If the ground point is not reserved, connect the device to the ground busbar directly.
  • On customized cabinets, porosity must be greater than 50% on the front and rear doors.
  • If a device uses front and rear access modes, it cannot be installed against a wall. This is to ensure that at least 760 mm of space is available for maintenance.