This document of the NIP6800 Series describes hardware structure, installation guide, and hardware maintenance. The content of this document includes the appearance and specifications of the product, the supported expansion cards, preparation before the installation, installation, cabling, and hardware replacement.
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Requirements for Temperature, Humidity, and Altitude

Requirements for Temperature, Humidity, and Altitude

Ensure proper temperature and humidity in the equipment room. Ensure the altitude of the equipment room in the regulated range. Table 4-10 lists the temperature, humidity, and altitude requirements for the equipment room.
Table 4-10  Requirements for temperature, humidity, and altitude

Item

Requirements

Environmental temperaturea

Long-term operationb

0°C to 45°C

Short-term operation

-5°C to 50°C

Storage temperature

-40°C to 70°C

Environmental relative humidity

Long-term operation

5% RH to 85% RH, no coagulation

Short-term operation

5% RH to 95% RH, no coagulation

Storage relative humidity

0% to 95%

Long-term altitude

Less than 3,000 m

Storage altitude

Less than 5,000 m

NOTE:
  • a. Temperature and humidity should be measured at a height of 1.5 m above the floor and 0.4 m away from the front of the cabinet. There should be no protection boards at the front or back of the cabinet.
  • b. Short-term operation means that the continuous running time of devices does not exceed 96 hours and the accumulated time of continuous running does not exceed 15 days per year. Running time that exceeds these parameters is considered long-term operation.
To meet the preceding requirements, take the following measures:
  • Use a perennial temperature-control device regardless of the local climate.
  • Mop the ground regularly or use a humidifier to maintain proper humidity in dry areas of in the equipment room.
  • Use a dehumidifier where the humidity is high.