This document describes the SUN2000-3KTL-M0, SUN2000-4KTL-M0, SUN2000-5KTL-M0, SUN2000-6KTL-M0, SUN2000-8KTL-M0, SUN2000-10KTL-M0, and SUN2000-12KTL-M0 in terms of their installation, electrical connections, commissioning, maintenance, and troubleshooting. BOM number: 01074467, 01074295, 01074300, 01074301, 01074302, 01074306, 01074311, 01074314, 01074315, 01074316, 01074320
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Connecting the AC Output Power Cable

Connecting the AC Output Power Cable

Precautions

A three-phase AC switch needs to be installed on the AC side of the SUN2000. To ensure that the SUN2000 can safely disconnect itself from the power grid when an exception occurs, select a proper overcurrent protection device in compliance with local power distribution regulations.

Do not connect loads between the SUN2000 and the AC switch.

The SUN2000 is integrated with a comprehensive residual current monitoring unit. Once detecting that the residual current exceeds the threshold, the SUN2000 immediately disconnects itself from the power grid.

  • If the external AC switch can perform earth leakage protection, the rated leakage action current should be greater than or equal to 100 mA.
  • If multiple SUN2000s connect to the general residual current device (RCD) through their respective external AC switches, the rated leakage action current of the general RCD should be greater than or equal to the number of SUN2000s multiplied by 100 mA.
  • A knife switch cannot be used as an AC switch.

Procedure

  1. Connect the AC output power cable to the AC connector.

    Figure 5-4 Stripping requirements
    • Ensure that the cable jacket is inside the connector.
    • Ensure that the exposed core wire is totally inserted into the cable hole.
    • Ensure that AC terminations provide firm and solid electrical connections. Failing to do so may cause SUN2000 malfunction and damage to its AC connectors.
    • Ensure that the cable is not twisted.
    Figure 5-5 Three-core cable (L1, L2, and L3)
    Figure 5-6 Four-core cable (L1, L2, L3, and PE)
    Figure 5-7 Four-core cable (L1, L2, L3, and N)
    Figure 5-8 Five-core cable (L1, L2, L3, N, and PE)
    NOTE:

    The cable colors shown in the figures are for reference only. Select an appropriate cable according to local standards.

  2. Connect the AC connector to the AC output port.

    Ensure that the AC connector is connected securely.

    Figure 5-9 Securing the AC connector

  3. Check the route of the AC output power cable.

    Figure 5-10 Cable route

Disconnection

Disconnection can be performed in reverse order.