No relevant resource is found in the selected language.

This site uses cookies. By continuing to browse the site you are agreeing to our use of cookies. Read our privacy policy>Search

Reminder

To have a better experience, please upgrade your IE browser.

upgrade

AMI Smart Meter Reading Solution V200R010C10 Planning and Design Guide

This document describes the overall and detailed design of functions and services in the AMI Smart Meter Reading Solution.
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
PLC Meter Parameter Plan

PLC Meter Parameter Plan

A PLC meter exchanges data with a DCU over a PLC link, and supports HDLC-based DLMS. Table 6-13 describes the PLC meter parameter plan.
Table 6-13  PLC meter parameter plan

Item

Parameter

Description

Profile parameters

Device model

The value is composed of the communication protocol plus the device model, for example, PLC-DLMS-CL710K11.

ESN

The ESN is the 20-digit code of a PLC meter and consists of letters and digits.

SN

The value is the 11-digit or 12-digit code of a PLC meter before delivery.

Asset name

Name of a PLC meter. The value is user-defined based on the actual name and cannot contain special characters.

Factory code

Name of the manufacturer. For example, the EEM supports the CLOU's PLC meter profile, so the value of this parameter is CLOU.

Organization name

Name of an organization that a PLC meter belongs to. If the organization name is not specified during PLC meter profile creation, the PLC meter belongs to the organization default by default. After the profile is created, the organization can be changed.

DCU

DCU that a PLC meter is directly connected or belong to.

Communications parameters

Logical Device Name

The value consists of HWT1 plus a string of 12 digits. If the SN of a DLMS meter is a string of 12 digits, the system appends HWT1 before the SN to generate a logical device name. If the SN of a DLMS meter is a string of 11 digits or letters, the system appends HWT1 before the SN and 0 after the SN.

Password

Low-level encryption key

The low-level and high-level authentication passwords used for communication between PLC meters and a DCU or a DCC contain 6 to 16 characters that allow only letters and digits. The passwords can be configured based on site survey data. If the passwords are not configured, the default password Admin@huawei is used.

High-level encryption key

Authentication level

Authentication level used for communication between PLC meters and a DCU or a DCC. There are three authentication modes: high-level authentication, low-level authentication, and non-authentication.

Encryption algorithm

Encryption algorithm used for communication between PLC meters and the DCU. The value can be Advanced Encryption Standard (AES)-128, AES-256, or Secure Hash Algorithm (SHA)-256. You can specify an encryption algorithm based on the network situation.