No relevant resource is found in the selected language.

This site uses cookies. By continuing to browse the site you are agreeing to our use of cookies. Read our privacy policy>Search

Reminder

To have a better experience, please upgrade your IE browser.

upgrade

SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1) User Manual

This document describes the SUN2000-175KTL-H0,SUN2000-185KTL-INH0, and SUN2000-185KTL-H1 in terms of their installation, electrical connections, commissioning, maintenance, and troubleshooting. BOM number: 01074671, 01074684, 01074687
Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Troubleshooting

Troubleshooting

Alarm severities are defined as follows:
  • Major: The inverter is faulty. As a result, the output power decreases or the grid-tied power generation is stopped.
  • Minor: Some components are faulty without affecting the grid-tied power generation.
  • Warning: The inverter works properly. The output power decreases or some authorization functions fail due to external factors.
Table 8-1 Common alarms and troubleshooting measures

Alarm ID

Alarm Name

Alarm Severity

Cause

Troubleshooting Suggestions

2001

High String Input Voltage

Major

The PV array is not properly configured. Excessive PV modules are connected in series to a PV string, and therefore the PV string open-circuit voltage exceeds the maximum operating voltage of the inverter.
  • Cause ID 1: PV strings 1 and 2
  • Cause ID 2: PV strings 3 and 4
  • Cause ID 3: PV strings 5 and 6
  • Cause ID 4: PV strings 7 and 8
  • Cause ID 5: PV strings 9 and 10
  • Cause ID 6: PV strings 11 and 12
  • Cause ID 7: PV strings 13 and 14
  • Cause ID 8: PV strings 15 and 16
  • Cause ID 9: PV strings 17 and 18

Reduce the number of PV modules connected in series in the PV string until the PV string open-circuit voltage is not greater than the maximum operating voltage of the inverter. After the PV array configuration is corrected, the alarm disappears.

2011

String Reverse Connection

Major

The PV string is reversely connected.

Cause ID 1–18: PV strings 1–18

Check whether the PV string is reversely connected to the inverter. If yes, wait until the PV string current drops below 0.5 A. Then, set all DC switches to OFF and correct the PV string connection.

2012

String Current Backfeed

Warning

  1. Only a few PV modules are connected in series in the PV string. Therefore, the end voltage is lower than that of other PV strings.
  2. The PV string is shaded.

Cause ID 1–18: PV strings 1–18

  1. Check whether the number of PV modules connected in series in the PV string is less than that in other PV strings connected in parallel with this PV string. If yes, wait until the PV string current drops below 0.5 A, set all DC switches to OFF, and adjust the number of PV modules in the PV string.
  2. Check whether the open-circuit voltage of the PV string is normal.
  3. Check whether the PV string is shaded.

2013

Abnormal String Power

Warning

  1. The PV string is shaded from sunlight for a long time.
  2. The PV string has aged abnormally.

Cause ID 1–18: PV strings 1–18

  1. Check whether the current of the abnormal PV string is lower than that of other PV strings. If it is, check whether the abnormal PV string is shaded and the actual number of PV strings is the same as the configured number.
  2. If the abnormal PV string is clean and not shaded, check whether the PV string is damaged.

2015

PV String Loss

Warning

This alarm is generated when the PV string status is abnormal in the following conditions:

  • A single PV string is lost.
  • Both 2-in-1 PV strings are lost.
  • Either of the 2-in-1 PV strings is lost.

Cause ID 1–8: PV strings 1–18

  1. If the PV string access type is manually set, check whether it is consistent with the actual access status.
  2. Check whether the inverter terminals are properly connected.
  3. Check whether the PV string terminals are properly connected.
  4. If a 2-in-1 terminal is used, check whether it is normal.

2031

Phase Wire Short-Circuited to PE

Major

Cause ID=1

The impedance of the output phase wire to PE is low or the output phase wire is short-circuited to PE.

Check the impedance of the output phase wire to PE, locate the position with lower impedance, and rectify the fault.

2032

Grid Loss

Major

Cause ID=1

  1. The power grid experiences an outage.
  2. The AC circuit is disconnected or the AC switch is off.
  1. The alarm is automatically cleared after the power grid is restored.
  2. Check whether the AC circuit is disconnected or the AC switch is off.

2033

Grid Undervoltage

Major

Cause ID=1

The grid voltage is below the lower threshold or the undervoltage duration has exceeded the time that triggers LVRT.

  1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers after detecting that the power grid becomes normal.
  2. If the alarm occurs frequently, check whether the power grid voltage is within the acceptable range. If not, contact the local power operator. If yes, modify the grid undervoltage protection threshold through the mobile app, SmartLogger, or network management system (NMS) with the consent of the local power operator.
  3. If the fault persists for a long time, check the AC circuit breaker and AC output power cable.

2034

Grid Overvoltage

Major

Cause ID=1

The grid voltage is beyond the upper threshold or the overvoltage duration has exceeded the time that triggers HVRT.

  1. Check whether the grid connection voltage exceeds the upper threshold. If yes, contact the local power operator.
  2. If you have confirmed that the grid-tied voltage exceeds the upper threshold and have obtained the consent of the local power operator, modify the overvoltage protection threshold through the mobile app, SmartLogger, or NMS.
  3. Check whether the peak grid voltage exceeds the upper threshold.

2035

Grid Voltage Imbalance

Major

Cause ID=1

The difference between grid phase voltages exceeds the upper threshold.

  1. Check that the grid voltage is within the normal range.
  2. Check that the AC output power cable is correctly connected. If the AC output power cable is correctly connected, yet the alarm persists and affects the energy yield of the power plant, contact the local power operator.

2036

Grid Overfrequency

Major

Cause ID=1

Power grid exception: The actual power grid frequency is higher than the standard requirement for the local power grid.

  1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers after detecting that the power grid becomes normal.
  2. If the alarm occurs frequently, check whether the power grid frequency is within the acceptable range. If not, contact the local power operator. If yes, modify the grid overfrequency protection threshold through the mobile app, SmartLogger, or NMS with the consent of the local power operator.

2037

Grid Underfrequency

Major

Cause ID=1

Power grid exception: The actual power grid frequency is lower than the standard requirement for the local power grid.

  1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers after detecting that the power grid becomes normal.
  2. If the alarm occurs frequently, check whether the power grid frequency is within the acceptable range. If not, contact the local power operator. If yes, modify the grid underfrequency protection threshold through the mobile app, SmartLogger, or NMS with the consent of the local power operator.

2038

Unstable Grid Frequency

Major

Cause ID=1

Power grid exception: The actual grid frequency change rate does not comply with the local power grid standard.

  1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers after detecting that the power grid becomes normal.
  2. If the alarm occurs frequently, check whether the power grid frequency is within the acceptable range. If not, contact the local power operator.

2039

Output Overcurrent

Major

Cause ID=1

The power grid voltage drops dramatically or the power grid is short-circuited. As a result, the inverter transient output current exceeds the upper threshold and therefore the inverter protection is triggered.

  1. The inverter detects its external working conditions in real time. After the fault is rectified, the inverter automatically recovers.
  2. If the alarm occurs frequently and affects the energy yield of the power plant, check whether the output is short-circuited. If the fault cannot be rectified, contact your dealer or Huawei technical support.

2040

Output DC Component Overhigh

Major

Cause ID=1

The DC component of the inverter output current exceeds the specified upper threshold.

  1. If the exception is caused by an external fault, the inverter automatically recovers after the fault is rectified.
  2. If this alarm occurs frequently and affects the energy yield of the PV plant, contact your dealer or Huawei technical support.

2051

Abnormal Residual Current

Major

Cause ID=1

The insulation impedance of the input side to PE decreases when the inverter is operating.

  1. If the alarm occurs occasionally, the external circuit may be abnormal temporarily. The inverter automatically recovers after the fault is rectified.
  2. If the alarm occurs frequently or persists, check whether the impedance between the PV string and the ground is too low.

2062

Low Insulation Resistance

Major

Cause ID=1

  1. The PV string is short-circuited to the PE cable.
  2. The PV string has been in a moist environment for a long time and the circuit is not well insulated to ground.
  1. Check the impedance of the PV string to PE. If a short circuit occurs, rectify it.
  2. Check that the ground cable of the inverter is correctly connected.
  3. If you are sure that the impedance is less than the preset value in a cloudy or rainy environment, reset Insulation resistance protection.

2063

Cabinet Overtemperature

Minor

Cause ID=1

  1. The inverter is installed in a place with poor ventilation.
  2. The ambient temperature is too high.
  3. The inverter is not working properly.
  1. Check the ventilation and whether the ambient temperature of the inverter exceeds the upper limit. If the ventilation is poor or the ambient temperature is too high, improve ventilation.
  2. If both the ventilation and ambient temperature meet requirements yet the fault persists, contact your dealer or Huawei technical support.

2064

Device Fault

Major

Cause ID=1

An unrecoverable fault has occurred on a circuit inside the inverter.

Turn off the AC output switch and DC input switch, and then turn them on after 15 minutes. If the fault persists, contact your dealer or Huawei technical support.

2065

Upgrade Failed or Software Version Unmatch

Minor

Cause ID=1

The upgrade does not complete normally.

  1. Perform an upgrade again.
  2. If the upgrade fails several times, contact your dealer.

2066

License Expired

Warning

Cause ID=1

  1. The privilege license has entered the grace period.
  2. The privilege feature will be invalid soon.
  1. Apply for a new license.
  2. Load a new license.

2086

External fan abnormal

Major

External fan short-circuited, power supply insufficient, or air channel blocked

Cause ID 1–3: fans 1–3

  1. Shut down the fan, turn off the DC switch, check whether the fan blades are damaged, and clear the foreign matter around the fan.
  2. Reinstall the fan, turn on the DC switch, and wait for the inverter to start. If the fault persists after 15 minutes, replace the external fan.

2087

Internal fan abnormal

Major

Cause ID=1

The internal fan is short-circuited, the power supply is insufficient, or the fan is damaged.

Turn off the AC output switch and then the DC input switch. Turn them on after 5 minutes and wait for the inverter to connect to the power grid. If the fault persists, contact your dealer or Huawei technical support.

61440

Faulty Monitoring Unit

Minor

Cause ID=1

  1. The flash memory is insufficient.
  2. The flash memory has bad sectors.

Turn off the AC output switch and DC input switch, and then turn them on after 15 minutes. If the fault persists, replace the monitoring board or contact your dealer or Huawei technical support.

NOTE:

If you cannot rectify faults with the measures listed in troubleshooting suggestions, contact your dealer or Huawei technical support.

Download
Updated: 2019-09-21

Document ID: EDOC1100083285

Views: 7199

Downloads: 607

Average rating:
This Document Applies to these Products
Related Documents
Related Version
Share
Previous Next