2001
|
High String Input Voltage
|
Major
|
The PV array is not properly configured. Excessive PV modules are connected in series to a PV string, and therefore the PV string open-circuit voltage exceeds the maximum operating voltage of the inverter. - Cause ID 1: PV strings 1 and 2.
- Cause ID 2: PV strings 3 and 4.
- Cause ID 3: PV strings 5 and 6.
- Cause ID 4: PV strings 7 and 8.
- Cause ID 5: PV strings 9 and 10.
- Cause ID 6: PV strings 11 and 12.
- Cause ID 7: PV strings 13 and 14.
- Cause ID 8: PV strings 15 and 16.
- Cause ID 9: PV strings 17 and 18.
|
Reduce the number of PV modules connected in series in the PV string until the PV string open-circuit voltage is not greater than the maximum operating voltage of the inverter. After the PV array configuration is corrected, the alarm disappears.
|
2011
|
String Reverse Connection
|
Major
|
The PV string is reversely connected.
Cause ID 1–18: PV strings 1–18
|
- Check whether the PV string is connected to the device in reverse polarity. If yes, wait until the PV string current decreases to below 0.5 A, set DC SWITCH to OFF, and adjust the PV string polarity.
- If the fault persists, reset the device on the local maintenance app or WebUI of the upper-layer controller. Alternatively, you can turn off the AC and DC switches, wait for 5 minutes, and then turn on the AC and DC switches.
|
2012
|
String Current Backfeed
|
Warning
|
Only a few PV modules are connected in series in the PV string. Therefore, the end voltage is lower than that of other PV strings.
Cause ID 1–18: PV strings 1–18
|
- Check whether the number of PV modules connected in series in the PV string is less than that in other PV strings connected in parallel with this PV string. If yes, wait until the PV string current drops below 0.5 A, set all DC switches to OFF, and adjust the number of PV modules in the PV string.
- Check whether the open-circuit voltage of the PV string is normal.
- Check whether the PV string is shaded.
|
2014
|
High input string voltage to ground
|
Major
|
Cause ID = 1
The voltage between the input PV modules and the ground is abnormal, and there is a risk of power degradation.
|
- If no PID compensation device exists in the system, disable the PID protection function at night. Note: If the PID protection function is disabled but reactive power compensation at night is enabled, PV modules may be degraded.
- If the system has a PID compensation device, check whether the device is abnormal. If yes, rectify the fault.
- Check whether the settings of compensation direction for the inverter and the PID compensation device are consistent. If not, set them to be consistent based on the PV module model. (Note: If the PV– is set to positive offset, the voltage between the inverter PV– and the ground should be greater than 0 V to clear the alarm; if the PV+ is set to negative offset, the voltage between the inverter PV+ and the ground should be less than 0 V to clear the alarm.)
- If the alarm persists, contact your dealer or Huawei technical support.
|
2015
|
PV String Loss
|
Warning
|
This alarm is generated when the PV string status is abnormal in the following conditions:
- A single PV string is lost.
- Both 2-in-1 PV strings are lost.
- Either of the 2-in-1 PV strings is lost.
Cause ID 1–8: PV strings 1–18
|
- If the PV string access type is manually set, check whether it is consistent with the actual access status.
- Check whether the inverter terminals are properly connected.
- Check whether the PV string terminals are properly connected.
- If a 2-in-1 terminal is used, check whether it is normal.
|
2031
|
Phase Wire Short-Circuited to PE
|
Major
|
Cause ID=1
The impedance of the output phase wire to PE is low or the output phase wire is short-circuited to PE.
|
Check the impedance of the output phase wire to PE, locate the position with lower impedance, and rectify the fault.
|
2032
|
Grid Loss
|
Major
|
Cause ID=1
- The power grid experiences an outage.
- The AC circuit is disconnected or the AC switch is off.
|
- The alarm is automatically cleared after the power grid is restored.
- Check whether the AC circuit is disconnected or the AC switch is off.
|
2033
|
Grid Undervoltage
|
Major
|
Cause ID=1
The grid voltage is below the lower threshold or the undervoltage duration has exceeded the time that triggers LVRT.
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid voltage is within the acceptable range. If not, contact the local power operator. If yes, modify the grid undervoltage protection threshold through the mobile app, SmartLogger, or network management system (NMS) with the consent of the local power operator.
- If the fault persists for a long time, check the AC circuit breaker and AC output power cable.
|
2034
|
Grid Overvoltage
|
Major
|
Cause ID=1
The grid voltage is beyond the upper threshold or the overvoltage duration has exceeded the time that triggers HVRT.
|
- Check whether the grid connection voltage exceeds the upper threshold. If yes, contact the local power operator.
- If you have confirmed that the grid-tied voltage exceeds the upper threshold and have obtained the consent of the local power operator, modify the overvoltage protection threshold through the mobile app, SmartLogger, or NMS.
- Check whether the peak grid voltage exceeds the upper threshold.
|
2035
|
Grid Voltage Imbalance
|
Major
|
Cause ID=1
The difference between grid phase voltages exceeds the upper threshold.
|
- Check that the grid voltage is within the normal range.
- Check that the AC output power cable is correctly connected. If the AC output power cable is correctly connected, yet the alarm persists and affects the energy yield of the power plant, contact the local power operator.
|
2036
|
Grid Overfrequency
|
Major
|
Cause ID=1
Power grid exception: The actual power grid frequency is higher than the standard requirement for the local power grid.
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid frequency is within the acceptable range. If not, contact the local power operator. If yes, modify the grid overfrequency protection threshold through the mobile app, SmartLogger, or NMS with the consent of the local power operator.
|
2037
|
Grid Underfrequency
|
Major
|
Cause ID=1
Power grid exception: The actual power grid frequency is lower than the standard requirement for the local power grid.
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid frequency is within the acceptable range. If not, contact the local power operator. If yes, modify the grid underfrequency protection threshold through the mobile app, SmartLogger, or NMS with the consent of the local power operator.
|
2038
|
Unstable Grid Frequency
|
Major
|
Cause ID=1
Power grid exception: The actual grid frequency change rate does not comply with the local power grid standard.
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The inverter automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid frequency is within the acceptable range. If not, contact the local power operator.
|
2039
|
AC Overcurrent
|
Major
|
Cause ID = 1
The grid experiences a dramatic voltage drop or is short-circuited. As a result, the transient AC current of the device exceeds the upper threshold and triggers protection.
|
1. The device detects its external working conditions in real time. After the fault is rectified, the device automatically recovers.
2. If the alarm occurs frequently and affects the operation of the power plant, check whether AC short circuit exists. If the fault persists, contact your dealer or technical support.
|
2040
|
Output DC Component Overhigh
|
Major
|
Cause ID=1
The DC component of the inverter output current exceeds the specified upper threshold.
|
- If the exception is caused by an external fault, the inverter automatically recovers after the fault is rectified.
- If this alarm occurs frequently and affects the energy yield of the PV plant, contact your dealer or Huawei technical support.
|
2051
|
Abnormal Residual Current
|
Major
|
Cause ID=1
The insulation impedance of the input side to PE decreases when the inverter is operating.
|
- If the alarm occurs occasionally, the external circuit may be abnormal temporarily. The inverter automatically recovers after the fault is rectified.
- If the alarm occurs frequently or persists, check whether the impedance between the PV string and the ground is too low.
|
2062
|
Low Insulation Resistance
|
Major
|
Cause ID=1
- The PV string is short-circuited to the PE cable.
- The PV string has been in a moist environment for a long time and the circuit is not well insulated to ground.
|
- Check the impedance of the PV string to PE. If a short circuit occurs, rectify it.
- Check that the ground cable of the inverter is correctly connected.
- If you are sure that the impedance is less than the preset value in a cloudy or rainy environment, reset Insulation resistance protection.
|
2063
|
Cabinet Overtemperature
|
Minor
|
Cause ID=1
- The inverter is installed in a place with poor ventilation.
- The ambient temperature is too high.
- The inverter is not working properly.
|
- Check the ventilation and whether the ambient temperature of the inverter exceeds the upper limit. If the ventilation is poor or the ambient temperature is too high, improve ventilation.
- If both the ventilation and ambient temperature meet requirements yet the fault persists, contact your dealer or Huawei technical support.
|
2064
|
Device Fault
|
Major
|
Cause ID = 1-5, 7-12, 20
A fault occurs on the internal inverter circuit.
|
Turn off the AC output switch and then the DC input switches. After 5 minutes, turn them on in the same sequence. If the fault persists, contact technical support.
Do not turn off the AC output switch or DC input switch. Contact your dealer or technical support.
|
2065
|
Upgrade Failed or Software Version Unmatch
|
Minor
|
Cause ID=1
The upgrade does not complete normally.
|
- Perform an upgrade again.
- If the upgrade fails several times, contact your dealer.
|
2066
|
License Expired
|
Warning
|
Cause ID=1
- The privilege license has entered the grace period.
- The privilege feature will be invalid soon.
|
- Apply for a new license.
- Load a new license.
|
2086
|
External fan abnormal
|
Major
|
External fan short-circuited, power supply insufficient, or air channel blocked
Cause ID 1–3: fans 1–3
|
- Shut down the fan, turn off the DC switch, check whether the fan blades are damaged, and clear the foreign matter around the fan.
- Reinstall the fan, turn on the DC switch, and wait for the inverter to start. If the fault persists after 15 minutes, replace the external fan.
|
2087
|
Internal fan abnormal
|
Major
|
Cause ID=1
The internal fan is short-circuited, the power supply is insufficient, or the fan is damaged.
|
Turn off the AC output switch and then the DC input switch. Turn them on after 5 minutes and wait for the inverter to connect to the power grid. If the fault persists, contact your dealer or Huawei technical support.
|
2088
|
Abnormal DC protection unit
|
Major
|
- Cause ID = 1
The fuse is not in position or is blown.
- Cause ID = 2
The two relays on the breaking board are open-circuited.
- Cause ID = 3
DC switch contact sticking.
|
- Cause ID = 1/2
Turn off the AC output switch and DC input switch, and then turn them on after 5 minutes. Wait for the inverter to connect to the power grid. If the alarm persists after 5 minutes, contact your dealer or Huawei technical support.
- Cause ID = 3
If the PV indicator (LED1) is off, contact your dealer or Huawei technical support to replace the device. If the PV indicator (LED1) is on, wait until the PV string current decreases to below 0.5 A. Then turn off the AC output switch and then the DC input switch. After 5 minutes, turn on the AC output switch and the DC input switch. Wait until the inverter connects to the power grid. If the fault persists 5 minutes later, contact your dealer or Huawei technical support.
|
2093
|
Abnormal DC Switches
|
Minor
|
Cause ID=1
The DC switch is not in the ON position, or the DC switch reset button is not pressed down to the bottom.
|
Check whether all DC switches are in the ON position. If not, turn the switches to the ON position (you can rotate the switches with force to ensure that they are in position). If the switches still cannot be turned to the ON position, press the reset buttons of all DC switches inwards until they cannot be moved further, and then turn on the DC switches again.
|
61440
|
Faulty Monitoring Unit
|
Minor
|
Cause ID=1
- The flash memory is insufficient.
- The flash memory has bad sectors.
|
Turn off the AC output switch and DC input switch, and then turn them on after 5 minutes. If the fault persists, replace the monitoring board or contact your dealer or Huawei technical support.
|