2001
|
High String Input Voltage
|
Major
|
- Cause ID = 1: PV1 and PV2
- Cause ID = 2: PV3 and PV4
- Cause ID = 3: PV5 and PV6
- Cause ID = 4: PV7 and PV8
- Cause ID = 5: PV9 and PV10
- Cause ID = 6: PV11 and PV12
- Cause ID = 7: PV13 and PV14
- Cause ID = 8: PV15 and PV16
- Cause ID = 9: PV17 and PV18
- Cause ID = 10: PV19 and PV20
The PV array is not properly configured. Excessive PV modules are connected in series to a PV string, and therefore the PV string open-circuit voltage exceeds the maximum operating voltage of the solar inverter.
|
Reduce the number of PV modules connected in series in the PV string until the PV string open-circuit voltage is not greater than the maximum operating voltage of the solar inverter. After the PV array configuration is corrected, the alarm disappears.
|
2003
|
DC arc fault
|
Major
|
Cause ID = 1–20: PV1–PV20
The PV string power cables arc or are in poor contact.
|
Check whether the PV string cables arc or are in poor contact.
|
2009
|
String Short-Circuited to Ground
|
Major
|
- A short circuit has occurred between the PV array and the ground.
- The ambient air of the PV array is damp and the insulation between the PV array and the ground is poor.
|
- Check the output-to-ground impedance of the PV array. If a short circuit or inadequate insulation is detected, rectify it.
- If auto recovery from string-to-ground short-circuit protection is disabled, check and rectify the preceding faults, and manually clear the alarm.
- If auto recovery from string-to-ground short-circuit protection is enabled, the alarm will be automatically cleared after fault recovery.
|
2011
|
String Reverse Connection
|
Major
|
Cause ID = 1–20: PV1–PV20
The PV string is reversely connected.
|
- Check whether the PV string is connected to the device in reverse polarity. If yes, wait until the PV string current decreases to below 0.5 A, set DC SWITCH to OFF, and adjust the PV string polarity.
- If the fault persists, reset the device on the local maintenance app or WebUI of the upper-layer controller. Alternatively, you can turn off the AC and DC switches, wait for 5 minutes, and then turn on the AC and DC switches.
|
2012
|
String Current Backfeed
|
Warning
|
Cause ID = 1–20: PV1–PV20
Only a few PV modules are connected in series in the PV string. Therefore, the terminal voltage is lower than that of other PV strings.
|
- Check whether the number of PV modules connected in series in the PV string is less than that in other PV strings connected in parallel. If yes, wait until the solar irradiance declines at night and the PV string current drops below 0.5 A. Then, turn off the DC switches and add more PV modules.
- Check whether the PV string is shaded.
- Check whether the open-circuit voltage of the PV string is normal.
|
2014
|
High Input String Voltage to Ground
|
Major
|
Cause ID = 1
The voltage between the input PV string and the ground is abnormal, and there is a risk of power attenuation.
|
- If no PID compensation device exists in the system, disable the PID protection function at night. Note: If the PID protection function is disabled but reactive power compensation at night is enabled, PV modules may attenuate.
- If there is a PID compensation device in the system, check whether it is faulty. If yes, rectify the fault.
- Check whether the settings of compensation direction for the solar inverter and the PID device are consistent. If not, set them to be consistent based on the PV module model. (Note: If the PV– is set to positive offset, the voltage between the solar inverter PV– and the ground should be greater than 0 V to clear the alarms; if the PV+ is set to negative offset, the voltage between the solar inverter PV+ and the ground should be less than 0 V to clear the alarms.)
- If the fault occurs frequently, contact technical support.
|
2015
|
PV String Loss
|
Warning
|
Cause ID = 1–20
This alarm is generated when the PV string status is abnormal due to the following conditions: a single PV string is lost; both 2-in-1 PV strings are lost; one of the 2-in-1 PV strings is lost.
|
- Check whether the solar inverter terminals are properly connected.
- Check whether the PV string terminals are properly connected.
- If a 2-in-1 terminal is used, check whether it is normal.
|
2021
|
AFCI self-check failure
|
Major
|
Cause ID = 1, 2
The AFCI self-check fails.
|
Turn off the AC output switch and then the DC input switches. After 5 minutes, turn them on in the same sequence. If the fault persists, contact technical support.
|
2031
|
Phase Wire Short-Circuited to PE
|
Major
|
Cause ID = 1
The impedance of the output phase wire to PE is low or the output phase wire is short-circuited to PE.
|
Check the impedance of the output phase wire to PE, locate the position with lower impedance, and rectify the fault.
|
2032
|
Grid Loss
|
Major
|
Cause ID = 1
- The power grid experiences an outage.
- The AC circuit is disconnected or the AC switch is off.
|
- Check the AC voltage.
- Check whether the AC circuit is disconnected or the AC switch is off.
|
2033
|
Grid Undervoltage
|
Major
|
Cause ID = 1
The grid voltage is below the lower threshold or the undervoltage duration exceeds the time that triggers low voltage ride-through (LVRT).
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The solar inverter automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid voltage is within the acceptable range. If not, contact the local power operator. If yes, log in to the mobile app, SmartLogger, or network management system (NMS) to modify the grid undervoltage protection threshold with the consent of the local power operator.
- If the fault persists for a long time, check the AC circuit breaker and AC output power cable.
|
2034
|
Grid Overvoltage
|
Major
|
Cause ID = 1
The grid voltage exceeds the upper threshold or the overvoltage duration exceeds the time that triggers high voltage ride-through (HVRT).
|
- Check whether the grid connection voltage exceeds the upper threshold. If yes, contact the local power operator.
- If you have confirmed that the grid connection voltage exceeds the upper threshold and have obtained the consent of the local power operator, modify the overvoltage protection threshold.
- Check whether the peak grid voltage exceeds the upper threshold.
|
2035
|
Grid Volt. Imbalance
|
Major
|
Cause ID = 1
The difference between grid phase voltages exceeds the upper threshold.
|
- Check that the grid voltage is within the normal range.
- Check that the AC output power cable is correctly connected. If the AC output power cable is correctly connected, yet the alarm persists and affects the energy yield of the PV plant, contact the local power operator.
|
2036
|
Grid Overfrequency
|
Major
|
Cause ID = 1
Power grid exception: The actual power grid frequency is higher than the standard requirement for the local power grid.
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The solar inverter automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid frequency is within the acceptable range. If not, contact the local power operator. If yes, log in to the mobile phone app, SmartLogger, or NMS to modify the power grid overfrequency protection threshold with the consent of the local power operator.
|
2037
|
Grid Underfrequency
|
Major
|
Cause ID = 1
Power grid exception: The actual power grid frequency is lower than the standard requirement for the local power grid.
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The solar inverter automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid frequency is within the acceptable range. If not, contact the local power operator. If yes, log in to the mobile phone app, SmartLogger, or NMS to modify the power grid underfrequency protection threshold with the consent of the local power operator.
|
2038
|
Unstable Grid Frequency
|
Major
|
Cause ID = 1
Power grid exception: The actual grid frequency change rate does not comply with the local power grid standard.
|
1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The solar inverter automatically recovers after detecting that the power grid becomes normal.
2. If the alarm occurs frequently, check whether the grid frequency is within the acceptable range. If not, contact the local power operator.
|
2039
|
AC Overcurrent
|
Major
|
Cause ID = 1
The grid experiences a dramatic voltage drop or is short-circuited. As a result, the transient AC current of the device exceeds the upper threshold and triggers protection.
|
1. The device detects its external working conditions in real time. After the fault is rectified, the device automatically recovers.
2. If the alarm occurs frequently and affects the operation of the power plant, check whether AC short circuit exists. If the fault persists, contact your dealer or technical support.
|
2040
|
Output DC Component Overhigh
|
Major
|
Cause ID = 1
The DC component of the solar inverter output current exceeds the specified upper threshold.
|
- If the exception is caused by an external fault, the solar inverter automatically recovers after the fault is rectified.
- If the alarm occurs frequently, contact your dealer or technical support.
|
2051
|
Abnormal Residual Current
|
Major
|
Cause ID = 1
The insulation impedance of the input side to PE decreases when the solar inverter is operating.
|
- If an alarm is generated, check whether the impedance between PV strings and the ground is too low, or a PV string is short-circuited to the ground due to damage.
- If the alarm occurs frequently or persists, check whether the impedance between the PV string and the ground is too low.
|
2061
|
Abnormal Grounding
|
Major
|
Cause ID = 1
The neutral wire or PE wire is not connected when Output mode of the solar inverter is set to Three-phase four-wire.
|
- Check that the neutral wire and PE wire of the solar inverter are properly connected.
- Check whether the voltage between the neutral wire and the ground exceeds 30 V. If yes, set Output mode to Three-phase three-wire on the mobile app, SmartLogger, or NMS after obtaining the consent of the local power operator.
|
2062
|
Low Insulation Resistance
|
Major
|
Cause ID = 1
- The PV string is short-circuited to PE.
- The PV string has been in a moist environment for a long time and the circuit is not well insulated to ground.
|
- Check the impedance of the PV string to PE. If a short circuit occurs or the insulation is insufficient, rectify it.
- Check that the PE cable of the solar inverter is correctly connected.
- If you are sure that the impedance is less than the default value in a cloudy or rainy environment, reset Insulation resistance protection.
|
2063
|
Cabinet Overtemperature
|
Minor
|
Cause ID = 1
- The solar inverter is installed in a place with poor ventilation.
- The ambient temperature is too high.
- The solar inverter is not working properly.
|
- Check the ventilation and whether the ambient temperature of the solar inverter exceeds the upper limit. If the ventilation is poor or the ambient temperature is too high, improve ventilation.
- If both the ventilation and ambient temperature meet requirements yet the fault persists, contact your dealer or technical support.
|
2064
|
Device Fault
|
Major
|
Cause ID = 1-5, 7-12, 20
A fault occurs on the internal inverter circuit.
|
Wait until the PV string current decreases to below 0.5 A, and then turn off all DC switches. If the fault persists, contact your dealer or technical support.
Turn off the AC output switch and then the DC input switches. After 5 minutes, turn them on in the same sequence. If the fault persists, contact technical support.
Do not turn off the AC output switch or DC input switch. Contact your dealer or technical support.
|
2065
|
Upgrade Failed or Software Version Unmatch
|
Minor
|
Cause ID = 1–4
The upgrade does not complete normally.
|
- Perform an upgrade again.
- If the update fails for multiple times, contact your dealer or technical support.
|
2066
|
License Expired
|
Warning
|
Cause ID = 1
- The privilege license has entered the grace period.
- The privilege feature will be invalid soon.
|
- Apply for a new license.
- Load a new license.
|
2067
|
Faulty Power Collector
|
Major
|
Cause ID = 1
The power meter is disconnected.
|
- Check whether the configured power meter model is the same as the actual model.
- Check whether the communications parameters of the power meter are the same as the RS485 configurations of the solar inverter.
- Check whether the power meter is powered on and whether the RS485 communications cable is connected.
|
2085
|
Built-in PID operation abnormal
|
Minor
|
Cause ID = 1, 2
- The output resistance of PV arrays to ground is low.
- The system insulation resistance is low.
|
- Cause ID = 1
- Turn off the AC output switch and DC input switch, wait for a period of time (for details about the wait time, see the description on the device safety warning label), and then turn on the DC input switch and AC output switch.
- If the fault persists, contact your dealer or technical support.
- Cause ID = 2
- Check the impedance between the PV array output and the ground. If a short circuit occurs or the insulation is insufficient, rectify the fault.
- If the fault persists, contact your dealer or technical support.
|
2086
|
External Fan Abnormal
|
Major
|
Cause ID = 1–3: FAN 1–3
The external fan is short-circuited, the power supply is insufficient, or the air channel is blocked.
|
- Shut down the fan, turn off the DC switch, check whether the fan blades are damaged, and clear the foreign matter around the fan.
- Reinstall the fan, turn on the DC switch, and wait for the solar inverter to start. If the fault persists after 15 minutes, replace the external fan.
|
2087
|
Internal Fan Abnormal
|
Major
|
Cause ID = 1
The internal fan is short-circuited, the power supply is insufficient, or the fan is damaged.
|
Turn off the AC output switch and then the DC input switch. Turn them on after 5 minutes and wait for the solar inverter to connect to the power grid. If the fault persists after 5 minutes, contact your dealer or technical support for replacement.
|
2088
|
Abnormal DC protection unit
|
Major
|
- Cause ID = 1
The fuse is not in position or is blown.
- Cause ID = 2
The two relays on the breaking board are open-circuited.
- Cause ID = 3
The contact points of the DC switches are stuck.
|
- Cause ID = 1/2
Turn off the AC output switch and DC input switch, and then turn them on after 5 minutes. Wait for the inverter to connect to the power grid. If the alarm persists after 5 minutes, contact your dealer or technical support.
- Cause ID = 3
If the PV indicator (LED1) is off, contact your dealer or technical support to replace the device. If the PV indicator (LED1) is on, wait until the PV string current decreases to below 0.5 A. Then turn off the AC output switch and then the DC input switch. After 5 minutes, turn on the AC output switch and the DC input switch. Wait until the inverter connects to the power grid. If the fault persists after 5 minutes, contact your dealer or technical support for replacement.
|
2093
|
Abnormal DC Switches
|
Minor
|
Cause ID=1
The DC switch is not in the ON position, or the DC switch reset button is not pressed down to the bottom.
|
Check whether all DC switches are in the ON position. If not, turn the switches to the ON position (you can rotate the switches with force to ensure that they are in position). If the switches still cannot be turned to the ON position, press the reset buttons of all DC switches inwards until they cannot be moved further, and then turn on the DC switches again.
|
61440
|
Faulty Monitoring Unit
|
Minor
|
Cause ID = 1
- The flash memory is insufficient.
- The flash memory has bad sectors.
|
Turn off the AC output switch and then the DC input switches. After 5 minutes, turn them on in the same sequence. If the fault persists, replace the monitoring board, or contact your dealer or technical support.
|