Check Before Power-on
Check Before Power-on
No.
Acceptance Criteria
1
The solar inverter is installed correctly and securely.
2
The DC switches and the downstream AC switch are OFF.
3
All cables are connected correctly and securely.
4
The installation space is proper, and the installation environment is clean and tidy.
5
The maintenance compartment door is closed and the door screws are tightened.
6
Unused DC input terminals are sealed.
7
Unused USB and RESET ports are plugged with watertight caps.