(Optional) Welding Pipes for the Low Temperature Component
Before welding pipes, take measures to protect nearby cables and components from being burnt.
To install a low temperature component horizontally, you are recommended to place the low temperature component on one side of the outdoor unit. Figure 4-66 and Figure 4-67 show the related inlet and outlet pipe ports. Install an inverted trap respectively at the inlet and outlet pipe ports on the outdoor unit condenser, preventing refrigerant from returning.
(1) Connecting to the indoor unit liquid pipe: 5/8 inch (15.88 mm) |
(2) Connecting to the outdoor unit liquid pipe: 5/8 inch (15.88 mm) |
(3) Connecting to the outdoor unit gas pipe: 7/8 inch (22.22 mm) |
(4) Connecting to the indoor unit gas pipe: 7/8 inch (22.22 mm) |